FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 1 1. PREFAŢĂ....................................................................................................................................................... 3 2. AVERTISMENT ............................................................................................................................................ 3 3. INFORMAŢII GENERALE ......................................................................................................................... 3 4. CONTACTE FĂRĂ POTENŢIAL............................................................................................................... 4 5. CONEXIUNI DE ALIMENTARE ............................................................................................................... 4 6. OPŢIUNEA DE START RAPID .................................................................................................................. 4 7. INSTRUCŢIUNI DE INSTALARE ............................................................................................................. 4 8. ÎNTREŢINERE ŞI VERIFICARE ............................................................................................................... 5 9. AFIŞAJUL DISPOZITIVULUI DE INTERFAŢĂ CU OPERATORUL (OID) ...................................... 6 STAREA SISTEMULUI. (AMBELE LIMBI)........................................................................................................ 10 JURNALE DE SISTEM. (AMBELE LIMBI) ......................................................................................................... 10 CONFIG. (AMBELE LIMBI) ................................................................................................................................. 10 10. ALIMENTAREA SISTEMULUI DE CONTROL .................................................................................... 11 11. TEST LAMPĂ.............................................................................................................................................. 11 12. RESETAREA ............................................................................................................................................... 11 13. FĂRĂ SUNET .............................................................................................................................................. 12 14. MONITORIZARE ALIMENTARE CU C.A. ........................................................................................... 12 ALIMENTARE CU C.A. NEREUŞITĂ ............................................................................................................. 12 15. RADIATOARE. ........................................................................................................................................... 12 RADIATOR MOTOR (OPŢIONAL). .................................................................................................................... 12 PANOU RADIATOR (OPŢIONAL). .................................................................................................................... 12 16. MONITORIZARE ALIMENTARE CU C.C. ........................................................................................... 13 TENSIUNEA ŞI CURENTUL BATERIEI ......................................................................................................... 13 DEFECTAREA BATERIEI................................................................................................................................ 13 17. BATERIA SE ÎNCARCĂ. ........................................................................................................................... 14 18. MONITORIZAREA ÎNCĂRCĂTORULUI .............................................................................................. 15 EROARE ÎNCĂRCĂTOR .................................................................................................................................. 15 19. MODUL MANUAL ..................................................................................................................................... 15 PORNIREA MANUALĂ ................................................................................................................................... 15 MOTOR ÎN FUNCŢIUNE.................................................................................................................................. 16 OPRIREA MOTORULUI (MANUAL). ............................................................................................................. 16 20. MODUL AUTOMAT................................................................................................................................... 16 PORNIRE AUTOMATĂ PRESIUNE SCĂZUTĂ ............................................................................................. 16 VALVĂ PENTRU INUNDAŢII......................................................................................................................... 17 PORNIRE DE LA DISTANŢĂ .......................................................................................................................... 17 MOTOR ÎN FUNCŢIUNE.................................................................................................................................. 17 OPRIRE MOTOR ÎN MODUL AUTO ............................................................................................................... 17 21. SECVENŢA DE DEMARARE ................................................................................................................... 18
Transcript

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 1

1. PREFAŢĂ ....................................................................................................................................................... 3

2. AVERTISMENT ............................................................................................................................................ 3

3. INFORMAŢII GENERALE ......................................................................................................................... 3

4. CONTACTE FĂRĂ POTENŢIAL ............................................................................................................... 4

5. CONEXIUNI DE ALIMENTARE ............................................................................................................... 4

6. OPŢIUNEA DE START RAPID .................................................................................................................. 4

7. INSTRUCŢIUNI DE INSTALARE ............................................................................................................. 4

8. ÎNTREŢINERE ŞI VERIFICARE ............................................................................................................... 5

9. AFIŞAJUL DISPOZITIVULUI DE INTERFAŢĂ CU OPERATORUL (OID) ...................................... 6

STAREA SISTEMULUI. (AMBELE LIMBI)........................................................................................................ 10

JURNALE DE SISTEM. (AMBELE LIMBI) ......................................................................................................... 10

CONFIG. (AMBELE LIMBI) ................................................................................................................................. 10

10. ALIMENTAREA SISTEMULUI DE CONTROL .................................................................................... 11

11. TEST LAMPĂ .............................................................................................................................................. 11

12. RESETAREA ............................................................................................................................................... 11

13. FĂRĂ SUNET .............................................................................................................................................. 12

14. MONITORIZARE ALIMENTARE CU C.A. ........................................................................................... 12

ALIMENTARE CU C.A. NEREUŞITĂ ............................................................................................................. 12

15. RADIATOARE. ........................................................................................................................................... 12

RADIATOR MOTOR (OPŢIONAL). .................................................................................................................... 12

PANOU RADIATOR (OPŢIONAL). .................................................................................................................... 12

16. MONITORIZARE ALIMENTARE CU C.C. ........................................................................................... 13

TENSIUNEA ŞI CURENTUL BATERIEI ......................................................................................................... 13

DEFECTAREA BATERIEI................................................................................................................................ 13

17. BATERIA SE ÎNCARCĂ. ........................................................................................................................... 14

18. MONITORIZAREA ÎNCĂRCĂTORULUI .............................................................................................. 15

EROARE ÎNCĂRCĂTOR .................................................................................................................................. 15

19. MODUL MANUAL ..................................................................................................................................... 15

PORNIREA MANUALĂ ................................................................................................................................... 15

MOTOR ÎN FUNCŢIUNE .................................................................................................................................. 16

OPRIREA MOTORULUI (MANUAL). ............................................................................................................. 16

20. MODUL AUTOMAT................................................................................................................................... 16

PORNIRE AUTOMATĂ PRESIUNE SCĂZUTĂ ............................................................................................. 16

VALVĂ PENTRU INUNDAŢII ......................................................................................................................... 17

PORNIRE DE LA DISTANŢĂ .......................................................................................................................... 17

MOTOR ÎN FUNCŢIUNE .................................................................................................................................. 17

OPRIRE MOTOR ÎN MODUL AUTO ............................................................................................................... 17

21. SECVENŢA DE DEMARARE ................................................................................................................... 18

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 2

EROARE BATERIE ÎN TIMPUL DEMARĂRII ............................................................................................... 18

PORNIRE NEREUŞITĂ .................................................................................................................................... 18

22. VITEZA EXCESIVĂ ................................................................................................................................... 19

23. PRESIUNEA SCĂZUTĂ A LUBRIFIANTULUI DIN MOTOR ............................................................ 19

24. TEMPERATURA RIDICATĂ A APEI DIN MOTOR. ........................................................................... 19

25. NIVELUL SCĂZUT AL CARBURANTULUI ÎN MOTOR .................................................................... 19

26. TEMPERATURA DE RĂCIRE SCĂZUTĂ ÎN MOTOR ....................................................................... 20

27. TEMPERATURA RIDICATĂ A APEI DE RĂCIRE ÎN MOTOR. ....................................................... 20

28. MOTOARE ELECTRICE .......................................................................................................................... 20

29. FILTRU DE APĂ ÎNFUNDAT ................................................................................................................... 21

30. REZERVOARE DE CARBURANŢI CU PEREŢI DUBLI ..................................................................... 21

31. PORNIRE TEST SĂPTĂMÂNAL. ............................................................................................................ 22

32. EROARE BOBINĂ CONECTOR .............................................................................................................. 22

33. OPRIRE MOTOR (V4.1) ............................................................................................................................ 22

34. CARD DE MEMORIE SD .......................................................................................................................... 22

35. MODURI SPECIALE DE OPERARE PENTRU FD4EU - OPŢIUNEA N1 .......................................... 24

36. ELIMINAREA. ............................................................................................................................................ 24

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 3

INSTRUCŢIUNI DE OPERARE A CONTROLERULUI: TIP: EFP/FD4e

1. PREFAŢĂ Acest manual de operare explică modul de operare a întregului sistem de control. 2. AVERTISMENT Pentru a evita riscul de VĂTĂMARE personală sau de daune asupra echipamentului de control, CITIŢI CU MULTĂ ATENŢIE ACEST MANUAL. Dacă mai aveţi dubii după citirea acestor instrucţiuni, nu ezitaţi să contactaţi Metron Eledyne pentru mai multe detalii. În vederea menţinerii siguranţei, acordaţi o atenţie deosebită notelor de AVERTISMENT menţionate mai jos: Dacă trebuie efectuate lucrări la motor sau la echipamentul de control, izolaţi echipamentul de control de sursele de alimentare cu c.a./c.c. şi deconectaţi alimentarea supapei solenoide de pornire de la bornele circuitului de comandă înainte de începerea lucrării. Dacă este posibil, utilizaţi o etichetă temporară care atrage atenţia asupra acestui fapt. Înainte de a încerca să porniţi motorul în timpul punerii în funcţiune, asiguraţi-vă că supapa solenoidă de oprire a alimentării cu carburant este funcţională. Având în vedere tipul de echipament, sistemul de control poate porni motorul în orice moment atunci când se operează în modul automat. Asiguraţi-vă că toţi cei implicaţi cunosc această condiţie cu ajutorul unei etichete adecvate, lipită pe şasiul motorului. Când echipamentul este alimentat şi „on line”, asiguraţi-vă că toate uşile sunt închise şi unde este cazul, blocate. Dacă în timpul punerii în funcţiune echipamentul este alimentat cu uşa de acces la interiorul panoului deschisă, asiguraţi-vă că toate capacele de bornă sunt fixate pentru a evita riscul de electrocutare. 3. INFORMAŢII GENERALE Controlerul este conceput ca un sistem complet automat de pornire a motorului conform cerinţelor prevăzute de Normele naţionale de protecţie împotriva incendiilor NFPA nr. 20 aferente controlerelor pentru pompe de incendiu acţionate de motor, IEC 62091, UL218 şi nr. de clasă FM 1321/1323. În aceste instrucţiuni, sunt utilizaţi următorii termeni după cum urmează: - Vizual lampă sau contor Afişaj afişaj LCD pe uşa din faţă (OID) Auditiv ecometru electronic

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 4

Contacte fără potenţial contacte de comutare de la distanţă fără potenţial 4. CONTACTE FĂRĂ POTENŢIAL Dacă este numit un contact fără potenţial, atunci titlul acestuia este activ de ex., Contact fără potenţial Motor în funcţiune Indică faptul că contactele se află în poziţia de motor în funcţiune. Dacă motorul în funcţiune cu contacte fără potenţial s-a oprit, de ex., Contact fără potenţial Motorul s-a oprit. Indică faptul că poziţia butoanelor s-a schimbat în poziţia standby (aşteptare) (motorul s-a oprit). 5. CONEXIUNI DE ALIMENTARE Asiguraţi-vă că sistemul este corect împământat şi faceţi interconexiunile pe baza informaţiilor cuprinse în schiţa de interconectare. Conectaţi sursele de alimentare la c.a/c.c. 6. OPŢIUNEA DE START RAPID Opţiunea de start rapid indică utilizatorului să configureze rapid ecranele principale pentru utilizarea corectă a controlerului pompei de incendiu. Această opţiune este lansată prin apăsarea şi menţinerea butonului „PILOT” timp de 2 sec. Apoi, trebuie să se completeze următoarele afişaje în ordinea care urmează: Pornire presiune Oprire presiune Amânare presiune Ora Data Ora de începere săptămânală Ziua de începere săptămânală Data stabilită Rezervor de carburant cu pereţi dubli Motor electric 7. INSTRUCŢIUNI DE INSTALARE A. Amplasare Controlerul va fi amplasat cât mai aproape şi mai convenabil de motorul diesel pe care îl monitorizează, având astfel şi câmp vizual. Controlerul nu trebuie amplasat direct sub ţevi din care ar putea să curgă apă. B. Montarea Controlerul trebuie montat folosind metode adecvate de fixare: Dacă controlerul este montat direct pe şasiul motorului, atunci trebuie utilizate montaje antiamortizante conform descrierii din desenul privind asamblarea generală (6 poziţii marcate cu „A”).

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 5

Dacă controlerul este montat pe un perete, atunci trebuie utilizate patru găuri interne de montare (sau console externe, dacă sunt furnizate). Trebuie utilizate dispozitive de fixare potrivite pentru perete, având în vedere greutatea controlerului, de aproximativ 52 kg. Se recomandă să se monteze controlerul la cel puţin 300 mm deasupra nivelului solului. Dacă se montează controlerul utilizând picioare opţionale (socluri), atunci controlerul trebuie fixat pe podea cu găurile de fixare prevăzute. Trebuie luate măsuri de precauţie pentru a vă asigura că controlerul nu este în apă. C. Conexiuni electrice Numai inginerii electrici cu experienţă vor efectua conexiunile electrice. Numai plăcuţa(ele) bucşei de presare a garniturii situate la baza monturii trebuie utilizată/e pentru aducerea cablurilor electrice. Placa presetupei trebuie scoasă din incintă în totalitate pentru perforarea orificiilor necesare pentru presetupă. În niciun caz nu trebuie utilizate alte zone ale incintei pentru aducerea cablurilor electrice. Presetupele corecte pentru cabluri trebuie utilizate pentru a asigura că sunt menţinute gradul de protecţie împotriva infiltrării şi integritatea incintei. Persoana care instalează are responsabilitatea de a asigura că niciun obiect metalic străin (cum ar fi aşchii provenite de la găurire etc.) nu cade în controler pe circuitul electric. Dacă nu se respectă acest lucru, se va putea produce deteriorarea controlerului, anulând astfel garanţia acestuia. Carcasa trebuie fixată în mod special, utilizând şuruburi de fixare pe pământ furnizate.

NOTĂ: Se recomandă în mod special, deşi nu este esenţial, să se aibă în vedere următoarele: Toate cablurile de semnal trebuie separate de sursele de alimentare. Acolo unde ambele trebuie să fie în apropiere, se recomandă să fie amplasate în unghiuri adecvate unul faţă de celălalt, reducând efectul de diafonie şi de zgomot. Cablurile de semnal vor fi mai puţin expuse turbulenţelor dacă sunt introduse în canalul de cabluri izolate şi împământate. Evitaţi trecerea cablurilor de semnal în apropierea surselor cunoscute de interferenţe sau a echipamentelor de înaltă tensiune, acolo unde este posibil. Asiguraţi zone curate de contact la fiecare finalizare de instalare şi utilizaţi cea mai practică grosime de cablu pentru a îmbunătăţi calitatea semnalului (se recomandă un cablu cu diametrul de maximum 2,5 mm pentru cablurile de semnal). 8. ÎNTREŢINERE ŞI VERIFICARE Trebuie să se efectueze verificări frecvente. Trebuie stabilit un program pentru verificările de întreţinere în funcţie de mediu şi de frecvenţa utilizării, dar ar trebui efectuate suficient de frecvent pentru a asigura faptul că echipamentul continuă să funcţioneze în modul stabilit. Se recomandă efectuarea unei verificări cel puţin o dată pe săptămână.

Părţile externe ale incintei trebuie curăţate periodic pentru a nu permite acumularea depunerilor de praf.

Toate componentele care sunt înlocuite trebuie să fie în conformitate cu specificaţiile producătorului. Neutilizarea acestor componente poate anula valabilitatea certificării/autorizării/garanţiei controlerului, determinând ca acesta să reprezinte un pericol.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 6

Panou indicator

Butoane de comandă

Afişaj LCD

Verificaţi ca toate bornele să fie fixate, iar distanţele de separare corecte să fie păstrate.

Toate declaraţiile, informaţiile tehnice şi recomandările din acest document se bazează pe informaţii şi teste pe care le-am considerat de încredere, corectitudinea şi complexitatea lor nefiind garantate în conformitate cu „Termenii şi condiţiile standard” ale Metron Eledyne. Deoarece aceste condiţii de utilizare nu intră în aria noastră de control, achizitorul trebuie să determine validitatea acestui produs în scopul pentru care a fost conceput şi îşi asumă orice risc şi obligaţie ce derivă din acestea în acest sens. 9. AFIŞAJUL DISPOZITIVULUI DE INTERFAŢĂ CU OPERATORUL (OID)

Dispozitivul de interfaţă cu operatorul (OID) asigură marcarea vizuală a alarmelor, starea parametrilor sistemului şi o interfaţă pentru a modifica valorile de referinţă privind configurarea FD4e, în vederea operării corecte a cerinţelor diverse de instalare.

Sarcini standard efectuate prin utilizarea OID

Semnalizatorul de atenuare a sunetului: Dacă un semnalizator sună, iar alarma reprezintă reducerea sunetului, printr-o apăsare rapidă a opţiunii [SILENCE/LAMPTEST] (REDUCERE SUNET/TEST LAMPĂ), semnalizatorul se va opri (apăsaţi pentru mai puţin de 1 secundă).

Resetarea alarmelor: Dacă starea alarmei a fost ştearsă, apăsaţi SCURT butonul [RESET/ESC] (RESETARE/ESC) pentru a reseta alarmele.

Modificarea modului de operare: Modul de operare a controlerului poate fi modificat prin comutatorul de mod şi prin apăsarea butoanelor de comandă OID. Când comutatorul de mod se află în poziţia „AUTO”

(automat), indicatorul „AUTO” va fi iluminat, iar controlerul se va afla numai în modul de start automat. Butonul de comandă Test este activ numai în timp ce comutatorul de mod se află în poziţia automată. Când comutatorul de mod se află în poziţia „MAN” (manual), indicatorul „MANUAL” va fi iluminat, iar controlerul se va afla numai în modul de start manual. Când comutatorul de mod se află în poziţia oprit, niciunul dintre indicatoarele AUTO sau MAN nu este iluminat.

Modul de testare: Când controlerul se află în modul Auto, apăsarea şi menţinerea butonului [TEST] timp de

două sau mai multe secunde va deschide supapa solenoidă a canalului de presiune reducând astfel presiunea care determină controlerul să oprească motorul. Apăsarea şi eliberarea butonului [TEST] în modul Manual controlează în mod direct deschiderea şi închiderea supapei solenoide a canalului. Motorul nu va porni automat atunci când se află în modul Manual.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 7

Test lampă: Pentru a ilumina şi verifica toate LED-urile OID şi semnalizatorul, apăsaţi şi menţineţi butonul [SILENCE/LAMPTEST] (REDUCERE SUNET/TEST LAMPĂ) timp de 5 sau mai multe secunde, până când se aprind luminile.

Controlerul poate fi configurat fie ca oprire „Manuală” sau „Automată” conform cerinţelor (ecranul System Config - Configuraţie sistem 104). Oprirea „Manuală” este setată ca standard. Starea actuală a acestei setări este vizibilă pe ecranul Main System Status (Stare sistem principal), unde litera „A” va apărea în colţul din dreapta sus al ecranului atunci când este setată oprirea automată, litera „M” va apărea când este setată oprirea manuală.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 8

2 CONFIG1) ANALOG SIGNALS2) AUXILLIARY ALARMS

1 CONFIG1) SYSTEM SETPOINTS2) USER PREFERENCES3) TECH SCREENS

# 1 EVENT DETAILS System in Off Mode Occurred 02/16/03 13:15:15

# 1 EVENT LOG System in Off Mode Occurred 02/16/03 13:15:15

# 1 EVENT DETAILS Pressure: 83.2psi System Auto:Yes Engine Running:No

# 1 EVENT DETAILS Charger #1 OK:Yes Charger #2 OK:Yes Battery #1 OK:Yes

# 1 EVENT DETAILS Battery #2 OK:Yes AC Power Avail:Yes Low Fuel Level:No

# 2 EVENT LOG Engine Failed ToStart Alarm Occurred

02/16/03 07:32:15

# 3 EVENT LOG AC Power Failure Alarm Cleared 02/16/03 07:09:48

PRESSURE LOG 02/16/03 17:52:45 112 psi Skip Rate:[EACH ]

PRESSURE LOG

02/16/03 17:52:30 112 psi Skip Rate:[EACH ]

PRESSURE LOG 02/16/03 17:52:15 113 psi Skip Rate:[EACH ]

SYSTEM LOGS1) Event Log2) Pressure Log

1 SYSTEM STATUS B1PRES STRT BAT1 BAT2110 100 13V 13V psi psi 6A 0A

3 SYSTEM STATUSEngine Countdown Tmr For AC Power Outage 0min Until Start

2 SYSTEM STATUSEngine Countdown Tmr 0sec Until Start 0min Until Stop

5 SYSTEM STATUSFirmware Ver SV 1.1Commissioned Date:

11/15/02

4 SYSTEM STATUSEngine Hrs: 5.3# Of Starts: 8Mon02/17/03 17:53:26

Continued on nextpage.

| || || |

| || || |

AUTO MANUAL TEST

STATUS

SYSTEM

LOGS

SYSTEM

1

CONFIG

2

METRON OID202

SILENCE

TEST

/LAMP

POWER

PRINT

3

ENTER

CHANGE/

ESC

RESET/

6 SYSTEM STATUSExtended VoltageBAT 1 27.10 0.00ABAT 2 27.05 0.00A

ON

LOSS OF DC POWER

OID Screen Map

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 9

Harta ecranului OID (continuare)

303 TECH SCREENS Energized To Stop Fuel Solenoid Time[10]seconds 0-99

304 TECH SCREENS Engine Condition Alarm Delay Time[10]seconds 1-99

305 TECH SCREENS Nominal Battery Voltage[24]VDC 10-99

306 TECH SCREENSBattery Low Voltage Alarm Trip Voltage[12.0]VDC 6-99

307 TECH SCREENSBattery Low Voltage Alarm Trip Time[ 2]seconds 0-99

308 TECH SCREENSChange Tech Password

[******]

309 TECH SCREENS Password Logout Time[ 5] minutes 1-15

317 TECH SCREENSAlarm Log 1/10

Event Log 1/1569Pr. Log 1/25123

316 TECH SCREENSAlarm resound timers4Hrs 0Min 0Sec24Hrs 0Min 0Sec

314 TECH SCREENS Load OID Hardware Test Mode[NO ]

313 TECH SCREENSAnnunciator Sequence

[STND]

310 TECH SCREENSSystem Commissioned Date

[31/12/99] DD/MM/YY

2 CONFIG1) ANALOG SIGNALS2) AUX USER PROGRAMS

1 CONFIG1) SYSTEM SETPOINTS2) USER PREFERENCES3) TECH SCREENS

207 USER PREFERENCES Time BetweenPressure Log Samples[ 15] seconds 15-999

206 USER PREFERENCESLow Pressure EventReset Time[15] seconds 0-20

205 USER PREFERENCESLow Pressure EventTrip Pressure[ 60.0]psi 0-999.9

204 USER PREFERENCESLog System Pressure Drop Events[Yes]

203 USER PREFERENCES Set System Day Of The Week[Sun]

202 USER PREFERENCES Set System Date

[08/10/10] DD/MM/YY

212 USER PREFERENCESLCD Back Light Mode 0=Always on[0]] 1=Power Save

213 USER PREFERENCESLanguage Select0=English, 1=Spanish[0]

214 USER PREFERENCESChange User PasswordLevel 1[****]

201 USER PREFERENCES Set System Real Time Clock[17:03:52]

102 SYSTEM SETPOINTS Engine Stop Pressure[110.0]psi 0-999.9

112 SYSTEM SETPOINTSPower Failure Engine Start Delay Time[ 1] minutes 0-500

117 SYSTEM SETPOINTS Shutdown On Low Intake Trip Time[ 20]seconds 0-999

116 SYSTEM SETPOINTS Shutdown On LowIntake Pressure/Lvl[No ]

115 SYSTEM SETPOINTS Shutdown On Low Intake Contact Type[NO ]

114 SYSTEM SETPOINTS Fail to start inputMB22 for unavailable[No ]

113 SYSTEM SETPOINTSPressure TransducerFailure Engine Start[Yes]

111 SYSTEM SETPOINTSPower Failure Engine Startup[No]

108 SYSTEM SETPOINTS Auto Weekly Engine Test Start Time[10:00:00]

109 SYSTEM SETPOINTS Auto Weekly Test Length Of Run Time[30] minutes 30-99

110 SYSTEM SETPOINTS Auto Weekly Test

Oil/Water Shutdown[No]

103 SYSTEM SETPOINTS Engine Start Delay Time[ 1] seconds 1-999

104 SYSTEM SETPOINTS Engine Automatic Stop Enabled[Yes]

105 SYSTEM SETPOINTS Engine Minimum Run Time[30]minutes 30-99

106 SYSTEM SETPOINTS Automatic Weekly Engine Test Run[No]

101 SYSTEM SETPOINTS Engine Start Pressure[100.0]psi 0-999.9

ANALOG INPUT COUNTS 649 1176 1221 12 12

422 ANALOG SIGNALSAnalog Input 3 1225Minimum Counts[ 0]

421 ANALOG SIGNALSAnalog Input 03Offset:[ 0.0000]

420 ANALOG SIGNALSAnalog Input 03Slope:[0.0352500]

412 ANALOG SIGNALSAnalog Input 2 1174Minimum Counts[ 0]

411 ANALOG SIGNALSAnalog Input 02Offset:[ 0.0000]

410 ANALOG SIGNALSAnalog Input 02Slope:[0.0352500]

402 ANALOG SIGNALSAnalog Input 1 651Minimum Counts[ 200]

401 ANALOG SIGNALSAnalog Input 01Offset:[- 76.1904]

400 ANALOG SIGNALSAnalog Input 01Slope:[0.3401360]

502 AUX SETPOINTSAux User Program # 1 Input Number[30] 0-70

512 AUX SETPOINTSAux User Program # 1 Output3 Number[ 0] 0-24

514 AUX SETPOINTSAux User Program # 1 Text Message Number[ 0] 0-32

513 AUX SETPOINTSAux User Program # 1 Record In Event Log[No ]

507 AUX SETPOINTSAux User Program # 1 Horn Enabled[No ]

511 AUX SETPOINTSAux User Program # 1 Output2 Number[ 0] 0-24

510 AUX SETPOINTSAux User Program # 1 Output1 Number[ 0] 0-24

508 AUX SETPOINTSAux User Program # 1 Horn Silence[No ]

509 AUX SETPOINTSAux User Program # 1 LED Number[ 0] 0-24

504 AUX SETPOINTSAux User Program # 1 Trip Time[ 0]sec 0-999

505 AUX SETPOINTSAux User Program # 1 Reset Time[ 0]sec 0-999

506 AUX SETPOINTSAux User Program # 1 Auto Reset Enabled[Yes]

503 AUX SETPOINTSAux User Program # 1 Input Contact Type[NO ]

501 AUX SETPOINTSAux User Program # 1 Enabled[No]

118 SYSTEM SETPOINTSLow Intake Shutdown Auto Reset[Yes]

121 SYSTEM SETPOINTS Deluge Valve Engine Start[Yes]

120 SYSTEM SETPOINTS Pressure Switch Engine Start[No ]

119 SYSTEM SETPOINTSLow Intake Shutdown Auto Reset Time[ 20]seconds 0-999

107 SYSTEM SETPOINTS Auto Weekly EngineTest Day Of The Week[Mon]

215 USER PREFERENCESSave ALL settingsto SD memory card[No ]

216 USER PREFERENCESLoad ALL settingsfrom SD memory card[No]

122 SYSTEM SETPOINTSHigh System Pressure Alarm[175.0]psi 999.9

424 BATTERY 1Constant AxA^3 + xB^2 + xC + D[ 0.0000]

425 BATTERY 1Constant BxA^3 + xB^2 + xC + D[ 0.0000]

426 BATTERY 1Constant CxA^3 + xB^2 + xC + D[ 0.00978]

427 BATTERY 1Constant DxA^3 + xB^2 + xC + D[- 0.05642]

432 BATTERY 2Constant CxA^3 + xB^2 + xC + D[ 0.00978]

433 BATTERY 2Constant DxA^3 + xB^2 + xC + D[- 0.05642]

431 BATTERY 2Constant BxA^3 + xB^2 + xC + D[ 0.0000]

430 BATTERY 2Constant AxA^3 + xB^2 + xC + D[ 0.0000]

428 BATTERY 1Volts per count

[1.0000000]

429 BATTERY 1Minimum Amps

[ 0.1]

435 BATTERY 2Minimum Amps

[ 0.1]

434 BATTERY 2Volts per count

[1.0000000]

318 TECH SCREENSDump ValveDelay time[0]s 0-999

217 USER PREFERENCESPressure Units

[bar]

218 USER PREFERENCESEngine Running chrgfailure alarm[No]

219 USER PREFERENCESCharger failuredelay time[ 5]seconds 0-999

220 USER PREFERENCESModbus Address

[ 1] 0-255

221 USER PREFERENCESRS485 com portSetting[Device ]

222 USER PREFERENCES

Modbus/Printer baud

[9600]

223 USER PREFERENCESModbus Parity

[None]

515 AUX SETPOINTSAux User Program # 1Engine Run Dependent[ ]

24v Defaults

319 TECH SCREENSPressureTransducer[Yes]

322 TECH SCREENSEngine OverspeedAlarm[3600]rpm 1000-9999

321 TECH SCREENSEngine Running Speed[600]rpm 200-999

320 TECH SCREENSWeekly Test Start Due Lamp Only[NO]

323 TECH SCREENSPulses PerRevolution[0] 0-999

FD4e v5.02

123 SYSTEM SETPOINTSEngine Lockout Latched[NO]

124 SYSTEM SETPOINTS Remote Start Input Contact Type[NO ]

324 TECH SCREENSMode Select0=US, 1=EU[1]

517 AUX SETPOINTSAux User Program # 1Include in First-Up[ ]

516 AUX SETPOINTSAux User Program # 1 Shutdown in Test[ ]

211 USER PREFERENCES Enable Remote Keypad[ No]

311 TECH SCREENSDOUBLE SKINNEDFUEL TANK[No]

312 TECH SCREENSELECTRONIC ENGINE

[Yes]

224 USER PREFERENCES RESTART

WIFI[No]

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(-)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(-)

(-)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(1)

(2)

(1)

(1)

(2)

(2)

(2)

(2)

(1)

(1)

(1)

(1)

(2)

(1)

(2)

(1)

(1)

(1)

(1)

(1)

(1)

(2)

(2)

(1)

(2)

(1)

(1)

(1)

(1)

(1)

(2)

(2)

(2)

(1)= level 2 password

(2)= level 2 password

(-)= no password

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 10

OID poate vizualiza 3 arii principale.

STAREA SISTEMULUI. (ambele limbi)

Când controlerul este comutat pe OID, va trece în mod implicit la ecranul 1 al stării de sistem care afişează presiunea flăcării principale; setarea presiunii de start; tensiunea şi curentul bateriilor 1 şi 2. JURNALE DE SISTEM. (ambele limbi)

În Jurnalele de sistem, este posibilă vizualizarea a 2 jurnale separate. Jurnale de eveniment (înregistrează alarme şi funcţii ale sistemului). Jurnale de presiune (înregistrează presiunea la intervalele setate). CONFIG. (ambele limbi)

În Config,. este posibilă vizualizarea a 5 zone diferite. Valori de referinţă sistem. (ambele limbi) Preferinţe utilizator. (ambele limbi) Ecran tehnic. (ambele limbi) Semnal analogic. (ambele limbi) Alarme auxiliare. (ambele limbi) Poate fi necesară modificarea Presiunii de start; acest lucru se poate efectua în Valorile de referinţă ale sistemului. Pentru a modifica Presiunea de start, apăsaţi în ordine următoarele butoane de comandă: Buton de configurare (2) o dată. Buton 1 (Jurnale de sistem) o dată. Buton Change/Enter (Modificare/Enter) o dată. Butoanele 1, 2 sau 3 pentru a introduce parola. Valoarea implicită este 1111. Butoanele Up (Sus) şi Down (Jos) pentru a modifica cifra. Change/Enter (Modificare/Enter) pentru a merge la următoarea cifră. Când noul număr este complet, apăsaţi Change/Enter (Modificare/Enter) pentru a accepta. Starea sistemului Verificaţi ca noua Presiune de start să fie corectă. Acum poate fi necesar să modificaţi Presiunea de oprire; pentru a face acest lucru, apăsaţi în ordine următoarele butoane. Buton de configurare (2) o dată. Buton 1 (Jurnale de sistem) o dată. Butoanele (Up) Sus şi (Down) Jos pentru a derula ecranele; mergeţi la 102. Buton Change/Enter (Modificare/Enter) o dată. Butoanele 1, 2 sau 3 pentru a introduce parola. Valoarea implicită este 1111.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 11

Butoanele Up (Sus) şi Down (Jos) pentru a modifica cifra. Change/Enter (Modificare/Enter) pentru a merge la următoarea cifră. Când noul număr este complet, apăsaţi Change/Enter (Modificare/Enter) pentru a accepta. Starea sistemului Verificaţi ca noua Presiune de oprire să fie corectă. Ecranele rămase nu sunt necesare pentru operarea standard a controlerului; dacă acestea sunt necesare, consultaţi Manualul de service. 10. ALIMENTAREA SISTEMULUI DE CONTROL Închideţi toate CB şi deschideţi izolatorul de c.a. Vizual Alimentare. Mod Auto (consultaţi nota). Baterie 1 Funcţională Baterie 2 Funcţională Auditiv. Fără sunet. Ecranul afişează: Presiunea apei Presiunea de start Baterie 1 Volţi şi Amp. Baterie 2 Volţi şi Amp. NOTĂ: Controlerul va alimenta în modul corespunzător comutatorului de mod. 11. TEST LAMPĂ Apăsaţi butonul Silence/Lamp test (Reducere sunet/Test lampă) timp de cel puţin 5 secunde; indicatorii se vor aprinde timp de 2 sec. şi apoi se vor stinge pentru 2 sec. Această procedură de stingere şi aprindere ciclică a indicatorilor va continua în timp ce butonul de testare a lămpii este apăsat, arătând că indicatorii pot fi porniţi şi opriţi. 12. RESETAREA Pentru a reseta o alarmă, apăsaţi butonul de comandă Reset/Esc (Resetare/Esc) timp de cel puţin 1 secundă.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 12

13. FĂRĂ SUNET Pentru a opri o alarmă, trebuie apăsat butonul Silence/Lamp Test (Reducere sunet/Test lampă) şi apoi eliberat. Opţiunea de reducere a sunetului opreşte acum semnalizatorul alarmei timp de 4 sau 24 de ore, în funcţie de sursa alarmei. După această perioadă, dacă alarma este încă prezentă, atunci semnalizatorul va fi reactivat. De exemplu: Aceste alarme au o opţiune de reducere a sunetului de 4 ore: Presiune scăzută a carburantului, temperatură ridicată a apei, pornire nereuşită, motor peste viteza limită. Aceste alarme au o opţiune de reducere a sunetului de 24 ore: Baterie nefuncţională, încărcător nefuncţional, nivel scăzut de carburant, temperatură scăzută a motorului. 14. MONITORIZARE ALIMENTARE CU C.A. Pornirea izolatorului de c.a. va alimenta disjunctorul încărcătorului de baterie CB1 şi CB5, care protejează circuitul din radiatorul motorului. ALIMENTARE CU C.A. NEREUŞITĂ

Dacă alimentarea cu c.a. nu reuşeşte, încărcătoarele bateriei nu vor mai fi alimentate, iar circuitul lor intern depistează acest lucru şi după un scurt interval. Vizual Pierdere de energie de c.a. (din cauza nereuşitei ambelor încărcătoare). Ulterior, după un interval de 30 de secunde. Vizual Eroare încărcător 1. Eroare încărcător 2. Eroare de sistem. Contact fără potenţial Eroare sistem. Auditiv. Fără sunet. La restabilirea alimentării cu c.a., se vor anula alarmele de furnizare de c.a. 15. RADIATOARE. RADIATOR MOTOR (Opţional).

Învelişul radiatorului de motor este protejat de CB5 şi, atunci când este pornit, va alimenta radiatorul motorului prin bornele L1 şi L2. PANOU RADIATOR (Opţional).

Alimentarea cu energie a panoului radiatorului este protejată de siguranţa fuzibilă F. Un termostat TH controlează panoul radiatorului. Cu termostatul TH peste temperatura ambiantă. Radiatorul se încălzeşte.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 13

Cu termostatul TH sub temperatura ambiantă. Radiatorul se răceşte. Setaţi termostatul la 30 de grade C. 16. MONITORIZARE ALIMENTARE CU C.C. TENSIUNEA ŞI CURENTUL BATERIEI

Tensiunea bateriei şi curentul de încărcare pot fi vizualizate pe ecranul LCD montat pe uşă. DEFECTAREA BATERIEI

Dacă o Baterie 1 este deconectată. Vizual Baterie 1 funcţională - porneşte Eroare de sistem. Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem. Când bateria a fost reconectată, controlerul trebuie să fie resetat pentru ştergerea alarmelor. Dacă o Baterie 2 este deconectată. Vizual Baterie 2 funcţională - porneşte Eroare de sistem. Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem. Când bateria a fost reconectată, controlerul trebuie să fie resetat pentru ştergerea alarmelor. Dacă ambele baterii sunt deconectate: Vizual Baterie 1 funcţională - porneşte Baterie 2 funcţională - porneşte Eroare sistem - pornit Pierdere alimentare cu c.c. - pornit Auditiv. Sunetul nu poate fi oprit. Contact fără potenţial Eroare sistem Nu este în modul Auto

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 14

17. BATERIA SE ÎNCARCĂ. Acest încărcător de baterie este conceput pentru utilizare exclusivă în cadrul sistemelor de control Metron Eledyne. Utilizarea unui adaptor/conector care nu este recomandat sau furnizat de Metron Eledyne poate duce la risc de incendiu, electrocutare sau vătămare corporală. Nu dezasamblaţi încărcătorul bateriei în niciun caz; nu există componente pentru utilizator în interior care să necesite service. Reasamblarea incorectă poate duce la risc de electrocutare sau la incendiu. AVERTISMENT Acţiunea încărcătorului bateriei este complet automată. Nu sunt furnizate variabile de operare, încărcătorul este configurat implicit din fabrică la tensiunea de menţinere, la un curent maxim de 10 A şi NU TREBUIE SĂ SE ÎNCERCE MODIFICĂRI LA FAŢA LOCULUI, putând rezulta astfel deteriorări ale bateriei. Întreţinerea bateriilor trebuie efectuată în conformitate cu instrucţiunile emise de producătorul de baterii. RISCUL GAZELOR EXPLOZIVE LUCRUL ÎN APROPIEREA BATERIILOR CU PLUMB ACID/NI-CD ESTE PERICULOS. BATERIILE GENEREAZĂ GAZE EXPLOZIVE ÎN TIMPUL OPERĂRII NORMALE. Pentru a reduce riscul explodării bateriei, citiţi acest manual în totalitate şi datele primite de la producătorii de baterii. Echipamentul utilizat în apropierea bateriilor trebuie, de asemenea, să fie selectat cu atenţie pentru a reduce riscul explodării bateriilor. MĂSURI PERSONALE DE PRECAUŢIE 1. Cineva trebuie să fie în apropierea dvs. pentru a vă auzi sau suficient de aproape pentru a veni în ajutorul dvs. atunci când lucraţi în apropierea unei baterii cu plumb acid/baterii Ni-Cd. 2. Asiguraţi-vă că aveţi la îndemână suficientă apă potabilă şi săpun în cazul în care acidul bateriei intră în contact cu pielea, hainele sau ochii. 3. Purtaţi ochelari şi haine de protecţie. Evitaţi contactul cu ochii în timp ce lucraţi în apropierea bateriei. 4. Dacă acidul bateriei intră în contact cu pielea sau hainele, spălaţi imediat cu apă şi săpun. Dacă acidul intră în ochi, clătiţi imediat cu multă apă rece de la robinet timp de cel puţin 10 minute şi solicitaţi consult medical de urgenţă. 5. NICIODATĂ nu fumaţi sau permiteţi să se producă scântei în apropierea bateriei sau a motorului. 6. Fiţi foarte precaut pentru a reduce riscul de cădere a unui instrument de metal pe baterie; acesta poate produce scântei sau scurtcircuita bateria sau alte componente electrice ce pot duce la explozie. 7. Scoateţi obiectele personale din metal cum ar fi inele, brăţări, coliere şi ceasuri atunci când lucraţi cu o baterie de motor. Astfel de baterii de motor pot determina un scurtcircuit destul de puternic pentru a suda un inel sau un obiect similar, provocând arsuri severe. 8. NICIODATĂ nu încărcaţi o baterie îngheţată. PREGĂTIREA PENTRU ÎNCĂRCARE Curăţaţi bornele bateriei. Aveţi grijă să preveniţi pătrunderea materialului coroziv în ochi. Consultaţi toate măsurile de precauţie specifice ale producătorilor de baterii, cum ar fi scoaterea sau păstrarea capacelor de celule în timpul încărcării iniţiale, şi verificaţi ca nivelul maxim de încărcare să nu fie depăşit.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 15

18. MONITORIZAREA ÎNCĂRCĂTORULUI

EROARE ÎNCĂRCĂTOR

Dacă încărcătorul 1 se opreşte din încărcare, circuitele sale interne vor depista acest lucru şi după un interval de 160 de secunde. Vizual Eroare încărcător 1. Eroare de sistem. Contact fără potenţial Eroare sistem. Auditiv. Fără sunet, timp de 24 de ore. Dacă încărcătorul începe să încarce din nou, alarmele de eroare a încărcătorului se vor anula. Dacă încărcătorul 2 se opreşte din încărcare, circuitele sale interne vor depista acest lucru şi după un interval de 160 de secunde. Vizual Eroare încărcător 2. Eroare de sistem. Contact fără potenţial Eroare sistem. Auditiv. Fără sunet, timp de 24 de ore. Dacă încărcătorul începe să încarce din nou, alarmele de eroare a încărcătorului se vor anula.

19. MODUL MANUAL Selectaţi modul Manual utilizând comutatorul de selectare a modului. Vizual Modul Manual. Modul Auto porneşte. NOTĂ: MODUL MANUAL TREBUIE UTILIZAT NUMAI PENTRU PUNEREA ÎN FUNCŢIUNE SAU PENTRU ÎNTREŢINERE. PORNIREA MANUALĂ

Pentru a începe, apăsaţi fie butoanele de comandă „Crank Battery 1” (Baterie de demarare 1), fie „Crank Battery 2” (Baterie de demarare 2), PB 1 sau PB 2; contactele acestora vor alimenta supapele solenoide de pornire prin bornele 9 sau 10 demarând motorul din bateria corespunzătoare. Încărcătoarele de baterie vor fi blocate şi, prin borna 1, supapa solenoidă a alimentării cu carburant va fi alimentată. Butoanele trebuie eliberate atunci când semnalizatorul luminos „Engine Running” (Motor în funcţiune) este aprins, ceea ce trebuie să se întâmple aproape imediat.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 16

MOTOR ÎN FUNCŢIUNE

Când motorul porneşte la viteză maximă, comutatorul de viteză conectat la unitatea de reglare a vitezei motorului va alimenta puterea de funcţionare a motorului, borna 2. Vizual Motor în funcţiune Contact fără potenţial Motor în funcţiune OPRIREA MOTORULUI (MANUAL).

Apăsarea butonului de comandă Engine Stop (Oprire motor) PB3 va determina ieşirea supapei solenoide la borna 12 (Energise to Stop), care este alimentată, iar ieşirea bornei 1 (Fuel Solenoid) nu mai este alimentată. 20. MODUL AUTOMAT Selectaţi modul Automat utilizând comutatorul de selectare a modului. Vizual Modul Automat. Modul Manual porneşte. Contact fără potenţial Modul automat.* *Notă: Când se pierde toată energia în controler, atunci contactele fără potenţial vor afişa mesajul „Not in Auto” („Nu este în modul Auto”). Controlerul este acum în poziţia Standby (Aşteptare). Pornirea manuală este interzisă. PORNIRE AUTOMATĂ PRESIUNE SCĂZUTĂ

Dacă presiunea apei pentru stingerea incendiului scade sub valoarea de referinţă a presiunii de pornire a motorului, cronometrul de amânare a pornirii motorului va fi alimentat. Când cronometrul semnalizează expirarea timpului, secvenţele de demarare vor începe alternativ de la ambele baterii prin bornele 9 sau 10, timp de 15 secunde. Presiunea de pornire a motorului poate fi setată din ecranul 101, System Setpoints (Valori de referinţă sistem). Presiunea de oprire a motorului poate fi setată din ecranul 102, System Setpoints (Valori de referinţă sistem). Cronometrul de amânare a pornirii motorului poate fi setat din ecranul 103, System Setpoints (Valori de referinţă sistem). NOTĂ: Presiunea de pornire TREBUIE să fie setată la o valoare mai mică decât cea de oprire. O secvenţă de demarare va începe alternativ de la ambele baterii prin bornele 9 sau 10, timp de

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 17

15 secunde. Vizual Pompare la cerere. Contact fără potenţial Pompare la cerere. Dacă semnalul de pornire este eliminat, secvenţa de demarare va continua. VALVĂ PENTRU INUNDAŢII

Dacă semnalul unei valve de inundaţii este primit în borna 16, cronometrul de amânare a pornirii motorului va fi alimentat. Când cronometrul semnalizează terminarea timpului, motorul va fi demarat alternativ de la ambele baterii prin bornele 9 sau 10, timp de 15 secunde. Vizual Pompare la cerere. Contact fără potenţial Pompare la cerere. Dacă semnalul de pornire este eliminat, secvenţa de demarare va continua. PORNIRE DE LA DISTANŢĂ

Dacă semnalul de pornire de la distanţă este primit la borna 17, o secvenţă de demarare va începe (fără amânare); motorul va fi demarat alternativ de la ambele baterii prin bornele 9 sau 10, timp de 15 secunde. Notă: intrarea pornirii de la distanţă poate fi selectată pentru pornire în mod normal, deschisă sau închisă, care se poate seta din ecranul 124. Vizual Pompare la cerere. Contact fără potenţial Pompare la cerere. Dacă semnalul de pornire este eliminat, secvenţa de demarare va continua. MOTOR ÎN FUNCŢIUNE

Când motorul porneşte la viteză maximă, comutatorul de viteză conectat la unitatea de reglare a vitezei motorului va alimenta puterea de funcţionare a motorului, borna 2; demararea va înceta imediat. Vizual Motor în funcţiune Contact fără potenţial Motor în funcţiune

OPRIRE MOTOR ÎN MODUL AUTO

Apăsarea butonului de comandă Engine Stop (Oprire motor) PB3 va determina ieşirea supapei solenoide la borna 12 (Energise to Stop), care este alimentată, iar ieşirea bornei 1 (Fuel Solenoid) nu mai este alimentată. Un SEMNAL DE PORNIRE AUTOMATĂ BLOCHEAZĂ butonul de comandă Engine

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 18

Shutdown (Oprire motor). 21. SECVENŢA DE DEMARARE După iniţierea secvenţei, încercările de demarare intervin alternativ de la fiecare baterie. Dacă sistemul de alimentare cu carburant a motorului este oprit şi demararea este permisă pentru a porni. Supapa solenoidă de demarare A alimentează timp de 15 sec. Demararea încetează pentru 15 sec. Supapa solenoidă de demarare B alimentează timp de 15 sec. Demararea încetează pentru 15 sec. Ciclul se repetă până când un număr total de şase încercări de demarare alternative au loc.

EROARE BATERIE ÎN TIMPUL DEMARĂRII

Când motorul de pornire demarează, tensiunea bateriei scade rapid la o valoare mai mică şi apoi revine la o valoare mai mare constantă în timpul demarării. Cu o baterie slabă, tensiunea rămâne mică. Demararea va fi transferată celeilalte baterii. PORNIRE NEREUŞITĂ

Când secvenţa de demarare a înregistrat şase încercări, va interveni o alarmă de pornire nereuşită. Vizual Motorul nu a pornit. Eroare de sistem. Contact fără potenţial Pornire nereuşită. Eroare sistem. Auditiv. Fără sunet, timp de 4 ore. Dacă se produce o alarmă de pornire nereuşită, iar semnalul de pornire este anulat, controlerul poate fi resetat pentru a reveni în modul de aşteptare (pentru a reseta, rotiţi comutatorul în poziţia „Off” (Oprit) şi apoi apăsaţi pe butonul de resetare). Dacă controlerul este resetat atunci când semnalul de pornire persistă, acesta va repeta secvenţele de demarare. Notă: Pe lângă cele de mai sus, ieşirea supapei solenoide de alimentare cu carburant, alimentarea pentru pornirea bornei 1, va rămâne astfel timp de 1 oră după pornirea nereuşită sau după setarea alarmei de oprire a motorului. Această opţiune este adaptată (şi solicitată de fabrică) în cazul unei erori a comutatorului de viteză şi deoarece motorul ar putea încă să mai funcţioneze. Pentru a anula cronometrul de 1 oră pentru supapa solenoidă de alimentare cu carburant, fie apăsaţi pe butonul de oprire, fie rotiţi comutatorul de mod în poziţia „Off” (Oprit) în orice moment.

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 19

22. VITEZA EXCESIVĂ Dacă se primeşte un semnal de viteză depăşită la borna 3, motorul se va opri, apoi, supapa solenoidă de alimentare cu carburant a motorului va opri carburantul. Motorul se opreşte. Modul Pornire automată este blocat, dar modul Pornire manuală este disponibil. Vizual Viteză excesivă motor. Disponibil pentru iniţiere Pornire automată. Contact fără potenţial Eroare sistem. Auditiv. Fără sunet, timp de 4 ore.

Controlerul rămâne blocat în starea de Viteză excesivă până când comutatorul de viteză de pe motor şi controler sunt resetate. 23. PRESIUNEA SCĂZUTĂ A LUBRIFIANTULUI DIN MOTOR Semnalul Motor în funcţiune activează alarma de presiune scăzută a carburantului şi este amânată pentru a permite presiunii să crească. După o amânare. Vizual Presiunea lubrifiantului din motor este scăzută. Contact fără potenţial Eroare sistem. Auditiv. Fără sunet, timp de 4 ore. 24. TEMPERATURA RIDICATĂ A APEI DIN MOTOR. Semnalul Motor în funcţiune activează alarma de temperatură ridicată a apei şi este amânată pentru a permite temperaturii să se stabilizeze. Vizual Temperatura apei din motor este ridicată. Contact fără potenţial Eroare sistem. Auditiv. Fără sunet, timp de 4 ore. 25. NIVELUL SCĂZUT AL CARBURANTULUI ÎN MOTOR Există o întârziere de 2 secunde înainte ca alarma pentru nivelul de carburant scăzut să se

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 20

activeze: Vizual Nivelul carburantului în motor este scăzut. Auditiv. Fără sunet, timp de 24 ore. Contact fără potenţial Eroare sistem 26. TEMPERATURA DE RĂCIRE SCĂZUTĂ ÎN MOTOR Dacă se indică temperatura de răcire în motor cu nivel redus, alarma se activează: Vizual Temperatura de răcire în motor este scăzută. Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem 27. TEMPERATURA RIDICATĂ A APEI DE RĂCIRE ÎN MOTOR. Semnalul Motor în funcţiune activează alarma de temperatură ridicată a apei de răcire şi este amânată pentru a permite temperaturii să se stabilizeze: Vizual Temperatura apei de răcire în motor este ridicată. Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem 28. MOTOARE ELECTRICE Dacă acţionarea motorului pompei de incendiu este de tip electronic, atunci trebuie adaptate următoarele 2 alarme suplimentare. Aceste alarme sunt activate prin selectarea opţiunii „Yes”

(Da) din ecranul 326. 28 A) Comutatorul de selectare ECM din alarma de poziţie alternativă. Dacă această alarmă este activată, atunci: Vizual Comutatorul de selectare ECM este în poziţia Alt. Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem 28 B) Alarmă defecţiune injector carburant. Dacă această alarmă este activată, atunci: Vizual Defecţiune injector carburant

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 21

Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem 28 C) Avertisment ECM. Dacă această alarmă este activată, atunci: Vizual Avertisment ECM Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem 28 D) Eroare ECM. Dacă această alarmă este activată, atunci: Vizual Eroare ECM Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem 29. FILTRU DE APĂ ÎNFUNDAT Semnalul Motor în funcţiune activează alarma de Filtru de apă înfundat şi este amânată pentru a permite sistemului să se stabilizeze: Vizual Temperatura filtrului de apă înfundat. Auditiv. Fără sunet, timp de 4 ore. Contact fără potenţial Eroare sistem 30. REZERVOARE DE CARBURANŢI CU PEREŢI DUBLI Dacă pompa de incendiu are un rezervor de carburant cu pereţi dubli, atunci trebuie adaptată o alarmă suplimentară. Această alarmă este activată prin selectarea opţiunii „Yes”(Da) din ecranul 325. Alarma suplimentară este pentru scurgeri de carburant din rezervor şi, dacă această alarmă trebuie activată, atunci: Vizual Scurgeri de carburant din rezervor Auditiv. Fără sunet, timp de 24 de ore. Contact fără potenţial Eroare sistem

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 22

31. PORNIRE TEST SĂPTĂMÂNAL. NFPA 20 menţionează că motorul trebuie să funcţioneze o dată pe săptămână timp de minimum 30 de minute. Setaţi cronometrul săptămânal de pornire; cronometrul de oprire poate fi setat utilizând ecranele 105 - 109 în System Setpoints (Valori de referinţă sistem). Când se activează cronometrul. O secvenţă de demarare este iniţiată. Motorul va rula acum în intervalul de timp pentru testul alocat şi apoi de oprire. 32. EROARE BOBINĂ CONECTOR Dacă bobinele conectorului motorului DC îşi pierd din continuitate (scurtcircuit sau circuit deschis) după o scurtă întârziere: Vizual Eroare bobină Auditiv. Fără sunet Contact fără potenţial Eroare sistem 33. OPRIRE MOTOR (V4.1) Dacă motorul se opreşte de la sine, fără ca controlerul să alimenteze supapa solenoidă de oprire pentru borna 12 (de la butonul de oprire, de la cronometrul de oprire automată sau prin oprirea funcţiilor de testare): Vizual Eroare sistem Auditiv. Fără sunet Contact fără potenţial Eroare sistem Pe lângă cele de mai sus, ieşirea supapei solenoide de alimentare cu carburant, alimentarea pentru pornirea bornei 1, va rămâne astfel timp de 1 oră după pornirea nereuşită sau după setarea alarmei de oprire a motorului. Această opţiune este adaptată (şi solicitată de fabrică) în cazul unei erori a comutatorului de viteză şi deoarece motorul ar putea încă să mai funcţioneze. Pentru a anula cronometrul de 1 oră pentru supapa solenoidă de alimentare cu carburant, fie apăsaţi pe butonul de oprire, fie rotiţi comutatorul de mod în poziţia „Off” (Oprit) în orice moment. 34. CARD DE MEMORIE SD Controlerul este dotat cu un card de memorie SD (Secure Digital) pentru placa de bază pentru a stoca jurnalul de presiune, jurnalul de evenimente şi informaţiile suplimentare de configurare a

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 23

alarmei. Cardul SD este localizat în marginea din dreapta a plăcii de bază şi este scos prin apăsarea înăuntru din partea dreaptă a cardului pentru a elibera cardul din suport. Când cardul SD este scos, datele sunt încă înregistrate pe un card de memorie temporară pe placa de bază. După înlocuirea cardului, datele stocate vor fi rescrise pe cardul SD. După scoaterea cardului SD, ecranul LCD va indica faptul că lipseşte cardul şi că trebuie înlocuit. Dacă nu se înlocuieşte cardul în aproximativ 1 minut, alarma se va activa prin aprinderea LED-ului de eroare sistem. După înlocuirea cardului SD, LED-ul de eroare de sistem se va stinge, dar butonul Alarm Silence (Alarmă fără sunet) trebuie apăsat pentru a opri semnalizatorul de alarmă. Datele stocate pe cardul SD sunt în format text standard ASCII şi pot fi citite de pe un computer echipat cu un cititor de carduri SD adecvat. Acestea sunt disponibile la orice magazin de electronice, dimensiunea maximă de utilizare fiind de 1 GB. Datele de pe cadrul SD sunt în următorul format: Fişier PressXXX.txt Acest fişier conţine un jurnal al presiunii apei, al tensiunii reale a bateriilor 1 şi 2 şi al curentului de ieşire real al încărcătoarelor 1 şi 2 şi este stocat din 15 în 15 secunde. Datele sunt stocate într-un fişier delimitat cu o virgulă standard, după cum urmează: 07/27/07, 11:07:52, 060 12.5 12.6 0.50 2.10 Data Ora Presiunea Curent încărcător baterie 2 Curent încărcător baterie 1 Tensiune baterie 2 Tensiune baterie 1 Fiecare fişier cu termenul „Press” (Apasă) conţine date cu privire la presiunea din timpul unei zile. XXX reprezintă data jurnalului de presiune. Fişier Events.txt Datele sunt stocate într-un fişier delimitat cu o virgulă standard, după cum urmează: 07/27/07 ,11:09:26 ,Tensiune scăzută baterie 2, Alarmă eliminată ,060 cont…… Data Ora Eveniment Acţiune Presiune 1, 0, 0, 0, 1, 1, 0, 0, 000 Modul Automat, Motor în funcţiune, Eroare încărcător 1, Eroare încărcător 2, Baterie 1 OK, Baterie 2 OK, Pierdere de energie c.a. Nivel redus de carburant Event Txt Ultimele 4 cifre ale fiecărui eveniment reprezintă tensiunea reală a bateriilor 1 şi 2 şi curentul de ieşire real al încărcătoarelor 1 şi 2

FD4e.v5.0 OPFD4e-V5.02 Iss 8, 20/01/2016 Metron Eledyne

F:\Engineering\Standards\1 D I E S E L\EFP-FD4e\FD4e v5.02\Manuals\Op-FD4e-v5.02-Romanian.doc 24

35. Moduri speciale de operare pentru FD4eU - Opţiunea N1 Când opţiunea N1 este adaptată la FD4eU, atunci dispozitivul de depistare a vitezei montat pe motorul diesel poate fi conectat direct la controler. Aceasta permite controlerului să identifice viteza reală printr-un modul electronic denumit PC257 - panou de control al vitezei. Când controlerul depistează viteza motorului, atunci ecranul de stare 1 va elimina presiunea de pornire a sistemului şi va afişa în schimb turaţia motorului. Pentru a configura această funcţie, se utilizează următoarele ecrane: 320 Viteza de funcţionare a motorului: 300-999 rpm Acesta indică controlerului valoarea turaţiei la care să oprească demararea motorului în modul automat (uneori denumită viteză de anulare a demarării). La această viteză motorul este definit ca funcţionabil. În mod normal, aceasta trebuie setată la 600 rpm. 321 Alarmă de viteză excesivă motor: 1.000-9.999 rpm Când viteza motorului depăşeşte această valoare, atunci este setată alarma de depăşire a vitezei şi motorul este oprit automat. Trebuie setat în conformitate cu NFPA 20 la viteza standard a motorului plus 20%. Reţineţi că, în scopul testării, această valoare poate fi setată temporar la o valoare mai mică pentru a verifica operarea sistemului motorului cu viteză excesivă. În orice caz, asiguraţi-vă că setaţi parametrul 321 de viteză excesivă a motorului la pragul cel mai ridicat la finalizarea testării. 322 Pulsuri per rotaţie: 0-999 Aceasta este o valoare de referinţă foarte importantă, deoarece sistemul utilizează această valoare împreună cu numărul de pulsuri primite de la motor pentru a determina turaţia reală a motorului. Reţineţi că, dacă motorul este deja echipat cu un comutator de viteză dedicat, atunci acest parametru 322 trebuie setat la 0, apoi borna 2 şi 3 trebuie conectate pentru a porni motorul şi a asigura condiţiile de viteză excesivă. 36. ELIMINAREA. Metron Eledyne este membră a programului de conformitate care respectă regulamentele privind deşeurile de echipamente electrice şi electronice, aplicabile în toate ţările CEE. La finalul ciclului de viaţă al echipamentului, compania se oferă să colecteze şi să elimine aceste echipamente în conformitate cu regulamentele în vigoare din cadrul nr. de înregistrare DEEE/CF0105WV. (Echipamentele trebuie ambalate în mod corect pentru a fi colectate de curier în afara Marii Britanii) Contact: Tel + 44 (0)1476 516120 Fax. + 44 (0)1476 516121.