SOLUTII INDUSTRIALE PENTRU ELIMINAREA PROGRESIVA A AGENTULUI FRIGORIFIC R22 Purtator de cuvant: Adrian Balaoi CSF, S.A. Sistemul Fri 3 Oil
Transcript
  • SOLUTII INDUSTRIALE PENTRU

    ELIMINAREA PROGRESIVA

    A AGENTULUI FRIGORIFIC R22

    Purtator de cuvant:

    Adrian Balaoi

    CSF, S.A. – Sistemul Fri3Oil

  • Cadru Juridic: Regulamente

    R.E. 1.005/2.0009

    •Este interzisa utilizarea agentului frigorific R-22 pentru intretinere in

    instalatiile RAC, din data de 1 Ianuarie 2.010

    •Este permisa utilizarea R-22 reciclat si/sau regenerat de la acea data

    pana la 31 Decembrie 2.014

    ESTE INTERZISA REVANZAREA PENTRU R-22, Reciclat si/sau Regenerat,

    de la 01-01-2.010

    •Identificati Modificarea Echipamentelor

    • Este permisa revanzarea pentru R22 regenerat

    Procedura Retrofit R-22

  • DATE DESPRE R-22

    In Spania inca exista 45.000 tns de R-22 in instalatii

    Scurgeri previzibile: 10% pe an

    80% din volum este in 20% din echipamente

    20% este in echipamente de dimensiuni mici

    STRATEGIE GENERALA

    Nu este necesar retrofit-ul masiv in scurt timp.

    Este interesant de a mentine 80% din instalatii cu agentul R22 existent

  • R-22

    Instalatie cu R-22

    IN SPANIA 55% DIN INSTALATII FUNCTIONEAZA CU R-22

    CARE SUNT SOLUTIILE?

  • Propuneri industriale:

    1. Eliminarea/Inlocuirea/Substituirea echipamentelor R-22.

    2. Produse “Drop -in”: R-417A,R-427A, R-422D, etc.

    3. Inlocuirea produselor cu POE sau PAG:

    - Agent frigorific R-404A. Temp. de vap. medie si scazuta.

    - R-407C A/A. Temp. de vaporizare inalta. -Clatiri POE.

    - Curatarea circuitului si HCF cu POE.

    •Este necesar sa se elimine MO pentru a evita fazele de

    separare, care dauneaza indicelui de vascozitate.

    Analizati instalatia inainte si dupa orice procedura RETROFIT.

  • Comparativ PROPUNERI AVANTAJE DEZAVANTAJE

    ECHIPAMENTE ELIMINATE SI INLOCUITE SIMPLU SI IN UNELE CAZURI CONVENABIL, PENTRU A EVITA COSTUL RETROFITULUI

    ECONOMIC NEVIABIL IN 100% DIN CAZURI

    REDUCERE DE NOI PRODUSE -SIMPLU, PRIN ALEGEREA CORECTA A PRODUSULUI

    - NU ESTE NECESAR SA EXISTE UN TEHNICIAN BINE

    INSTRUIT

    - OPERATIUNI LIMITATE:

    •RECUPERARE R-22

    •INTRODUCERE R-... DE LA UN PRODUCATOR

    SPECIFIC

    -COMPLICA LOGISTICA

    -DUBII: APLICARE, DISPONIBILITATE,

    PERFORMANTA TEMPORARA

    -“METODA BLIND”.

    -PRODUSE PATENTATE DOAR DE UN SINGUR

    PRODUCATOR

    “MARFURI”+ POE/PAG

    CLATIRI -METODA RAPIDA

    -PRODUSE:

    •TOTI PRODUCATORII

    •TEMP. SCAZUTA/MEDIE: R-404A (R-507)

    •TEMP. INALTA: R-407C

    •PRODUCERE RIDICATA DE REZIDUURI

    •COSTURI RIDICATE A FORTEI DE MUNCA

    •ELIMINARE INSUFICIENTA A REZIDUURILOR

    DIN INSTALATII

    •RISC DE DEFECTIUNE A COMPRESOARELOR

    •“METODA BLIND”

    • LIMITA MO/POE– “REFRACTOMETRU

    MANUAL”

    PROCEDURA CSF,SA

    ANALIZA ANTERIOARA SI RETROSPECTIVA A

    RETROFITULUI

    CURATARE TOTALA A INSTALATIEI

    PRODUS+POE/PAG + ADITIVI

    CLIMACHECK+SISTEM FRI3OIL +ZEROL ICE

    -ANALIZA INAINTE SI DUPA RETROFITTING

    -MAJORAREA CURATARII CU 8/10% CAP & COP

    -MAJORAREA DE ADITIVI CU 4-10% CAP & COP

    -RECUPERARE SI CURATARE AGENT FRIGORIFIC

    PENTRU REUTILIZARE

    -RAPORT TEHNIC ANTERIOR, INAINTE DE A LUA

    DECIZIA DE RETROFIT. MAI TARZIU RAPORT PENTRU

    CLIENT.

    -INSTALATOR PROFESIONIST

    -SIGURANTA SI SECURITATEA UTILIZATORULUI

    •OPRIREA INSTALATIEI PENTRU O PERIOADA

    DE TIMP

    •FUNCTIONARE ECONOMICA MAI MICA

  • Metoda retrofit propusa de: CSF,SA

    R-22

    Analiza prealabila

    a instalatiei

    Recuperare si Curatare

    HFC

    +

    POE

    +

    Aditiv

    Punere in functiune cu:

    HCF si POE + Aditiv

    Analiza si

    raport client CALCINARE

    REUTILIZARE

    INSCRIPTIE

    INREGISTRARE

    REZERVA

  • Analizele de Performanta sunt o posibilitate

    Bazat pe PC si/sau Web (sau manual daca se doreste): Punere in functiune – minimizarea costului de garantie Inspectie de performanta – optimizare Intretinere preventiva Testare

    Decizie de baza – expansiune, incarcare estimata, retrofit

    Provizorii sau fixe – Locale sau la distanta

    DIN-instalatie montata fix

  • Analize pe proces ”standard”

    1. Presiune scazuta si temp.

    de aspiratie a gazului.

    2. Presiune inalta si temp.

    de refulare a gazului.

    3. Presiune inalta si temp.

    lichidului.

    Implementarea teoriei la utilizarea practica in industrie

    1

    2 3

    Presiune

    Entalpie

    Compresiune ideala

    Cap. de racire

    Cap. de incalzire

    Putere absorbita

    P LP

    P HP

    Debit masic = puterea absorbita – pierderi de caldura/diferenta de entalpie a compresorului

    COP = Capacitate de racire/ Putere absorbita

  • Analizarea Performantei Teoriei utilizand

    metoda ”Cutia Neagra” pe compresor

    Cresterea entalpiei agentului frigorific

    Puterea absorbita

    Compresorul poate fi utilizat la un debit masic masurat

    Pierderi de caldura

    (relativ mici si previzibile)

    Puterea absorbita = cresterea entalpiei x debitul masic + pierderi de caldura prin carcasa

  • Castellana de

    Suministros

    Frigoríficos, S.A.

  • 2. Recuperare si curatare circuit

    Sistem Fri3Oil :

    •Brevetare Spaniola din 2005

    •20 de Tari: Europa si America de Sud •Recupereaza si curata orice agent firgorific halocarbon: CFC,

    HCFC & HCF

    •Eficienta energetica este imbunatatita prin curatarea circuitului intern

    •R-22 pentru service pana la sfarsitul anului 2014

    Procedura Retrofit R-22

  • Solutiile SISTEMULUI FRI3 OIL :

    •Date tehnice:

    – ELIMINARE REZIDUURI DE LA MOTOR COMPRESOR

    – CAND EXISTA APA IN INSTALATIE

    – RETROFITTING MO > POE

    – INSTALARE NOUA CU AGENTI DE CONTAMINARE A AERULUI POE

    – INTRETINERE PREVENTIVA PH

  • Solutiile SISTEMULUI FRI3 OIL :

    Procedura Retrofit R-22

    •MEDIU INCONJURATOR :

    – OAMENI

    •MEDIU FAVORABIL

    •SOLUTIE GLOBALA PENTRU DESEURI TOXICE

    –LEGI

    •RECUPERAREA SI RECICLAREA AGENTILOR

    FRIGORIFICI

    •RECICLARE UTILAJE

    •USURINTA DE ELIMINARE A REZIDUURILOR

  • Solutiile SISTEMULUI FRI3 OIL :

    Procedura Retrofit R-22

    ECONOMIC:

    – REUTILIZAREA AGENTILOR FRIGORIFICI

    – EVITAREA DISTRUGERII AGENTILOR FRIGORIFICI

    – EVITAREA SCURGERII AGENTILOR FRIGORIFICI

    – NU NECESITA CUMPARAREA AGENTILOR FRIGORIFICI NOI

    – GARANTIE FIABILA SI PROFESIONALA

    – ECONOMII DE NITROGEN USCAT

    – INCASARI DE LA SERVICE

    – ECONOMII CU FORTA DE MUNCA, UNITATI VRV.

  • PRINCIPII DE BAZA ALE SISTEMULUI DE CURATARE

    DIALIZA

    Procedura Retrofit R-22

    1.- MISCIBILITATE/SOLUBILITATE

    2.- DECANTARE DENSITATI

    3.- SEPARAREA LICHIDELOR PRIN

    VAPORIZAREA AGENTULUI FRIGORIFIC

  • PRINCIPII FIZICE ALE SISTEMULUI

    Procedura Retrofit R-22

  • 3. Aditivii Zerol ICE & ICE32

    •Scad frecarile

    •Reduc temp. de refulare

    •Extind durata de viata a

    compresorului

    •Reduc Consumul de Energie

    Electrica

    •Creste Capacitatea Ref.

    •Creste COP

    •Imbunatatire de 4-10%

  • STUDIU DE CAZ I

    CLIMATIZARE

    • Locul: Barcelona

    • Data: Iulie 2.009

    • Compania: Sodexo Facilities Management, S.A.

    • Echipament: Grup racire lichide apa/apa

    • 600kW, cu 2 circuite

  • Inregistrator cu

    ClimaCheck

  • Agent frigorific: R-22 Numar de Compresoare: 4 Numar de circuite: 2

    Incarcare agent frigorific: 2 x 54 Kgs

    Temp. de evacuare a apei

    Vaporizator (°C)

    Temp. de evacuare a apei

    Condensator (°C)

    Cap. de racire

    (kcal/h.)

    Putere

    (kW)

    5 30 494.000 142

    6 30 518.000 144

    8 30 564.000 146

    10 30 610.000 147

    12 30 656.000 148

    5 35 476.000 152

    6 35 498.000 154

    8 35 542.000 157

    10 35 586.000 160

    12 35 630.000 163

    5 40 440.000 162

    6 40 460.000 166

    8 40 502.000 169

    10 40 542.000 172

    12 40 584.000 175

    Tabel cu capacitate de racire, consumul de energie electrica, in ceea ce priveste temp. apei Condensatorului sau Vaporizatorului ΔT 5,5 °C, cu privire la manualul de service.

  • CAPACITATEA DE

    RACIRE SI PUTERE

    CAZ Capacitate de

    racire (Kw)

    Putere

    (Kw)

    R-22 240 76

    DROP IN 205 73

    R-407C 275 81

  • Vaporizator Admisie

    (°C)

    Evacuare

    (°C)

    R-22 13 - 16 10 - 12

    DROP IN 13 12

    R-407C 13 - 16 10 - 12

    ADMISIE si EVACUARE

    Vaporizator si Condensator

    (flux Sec)

    Condensator Admisie

    (°C)

    Evacuare

    (°C)

    R-22 26 - 28 30 - 32

    DROP IN 26 - 29 29 - 32

    R-407C 26 - 29 30 - 32

  • Temp. aspiratie, refulare

    si linia de lichid

    CAZ Aspiratie

    (°C)

    Lichid

    (°C)

    Refulare

    (°C)

    R-22 10 38 90

    DROP IN 14 37 78

    R-407C 7 37 70

  • Presiune Inalta si

    Presiune Scazuta

    CAZ LP (Bar) HP (Bar)

    R-22 3,8 – 4,5 14 – 15,5

    DROP IN 3,2 – 3,7 19 - 20

    R-407C 4,2 – 4,5 16 - 17

  • Supraincalzire si

    Subracire

    CAZ Recalent.

    (°C)

    Subenf.

    (°C)

    R-22 9,5 – 11,5 2,5 – 3,5

    DROP IN 15 10

    R-407C 1 – 2 2,3

  • CAZ Incalzire

    COP

    Racire

    COP

    R-22 4,1 3,2

    DROP IN 3,7 2,8

    R-407C 4,2 3,3

    Incalzire si racire COP

  • EFICIENTA IZENTROPICA

    CAZ I EFFI (%)

    R-22 62

    DROP IN 68

    R-407C 64

  • STUDIU DE CAZ II

    REFRIGERARE

    • Locul: Milano

    • Data: Februarie 2.010

    • Compania: S.C.A.R. Refrigerazione, srl.

    • Echipament: Centrala de compresoare de temperaturi pozitive pentru

    Hypermarket

    • 6 compresoare Bitzer, peste 200 terminale

  • TEMPERATURA MEDIE CENTRALA Agent frigorific: R-22 Numar de Compresoare: 6 Producator: BITZER Model: 6F-40.2Y

    Tabel pentru capacitati, consumuri si COP, in ceea ce priveste software-ul BITZER, pe unitate

    MODEL 6F-40.2

    (R-22)

    6F-40.2

    (R-22)

    6F-40.2

    (R-404A)

    6F-40.2

    (R-404A)

    Temp. de Vaporizare (°C) -16 -12 -15 -13

    Temp. de Condensare(°C) 33 26 20 20

    Cap. de Racire (kW) 66,1 83,5 92,7 101,5

    Putere consumata (kW) 24,0 23,4 24,3 24,8

    Temp. de Refulare (°C) 109,3 88,7 59,6 56,8

    COP 2,57 3,38 3,36 3,70

  • CAZ CAP.

    RACIRE

    (kW)

    PUTERE

    (kW)

    R-22 90 - 180 29 - 53

    R-404A 110 - 200 32 - 57

    CAPACITATE

    DE RACIRE SI PUTERE

  • VAPORIZARE

    (°C)

    CONDENSARE

    (°C)

    R-22 -16 / - 12 26 / 30

    R-

    404A

    -17 / - 13 19 - 20

    Temp. de

    Vaporizare si

    Condensare

  • Temp. Aspiratie,

    Refulare si

    linia de Lichid

    CAZ Aspiratie

    (°C)

    Lichid

    (°C)

    Refulare

    (°C)

    R-22 6 24 85

    R-404A 7 18 65

  • CAZ Racire

    COP

    R-22 3,0 – 3,4

    R-404A 3,2 – 3,6

    RACIRE COP

  • E.R. 842/2006

    Obiectiv:

    - Minimizarea emisiilor de gaze Fluorurate cu Efect de sera

    Masuri:

    - Certificare de etanseitate: E.R. 1516/2007

    - Plasarea unui Sistem de Detectare a Scurgerilor

    - Calificarea personalului

    Cadru Juridic. Regulamente

  • Dovezi de certificare a etanseitatii

    • Protocol E.R.1516/2007

    • in vigoare din 04/07/2007

    • Certificari:

    • 3/30kg ----- 1/an

    • 30/300kg ---- 2/an

    • >300kg ----- 4/an

  • Gaze fluorurate si Detectari Scurgeri

    Calificarea Personalului si a Companiilor

    Calificare de 4 tipuri

    In Spania sunt 2 tipuri de calificari

  • ULTRAPROBE100 KT1

    ULTRAPROBE100KT1

  • ULTRAPROBE100 KT1

    DETECTARE PRESIUNE

    DETECTARE VACUUM

    MICROSCURGERI

    VACUUM

  • Detectari Scurgeri

    ULTRAPROBE100 KT1

  • Detectari Scurgeri

    ULTRAPROBE100 KT1

  • Detectari Scurgeri

    ULTRAPROBE100 KT1

  • Frecventa Inalta

    Generator de Ton

    LLA

    Detectari Scurgeri

    ULTRAPROBE100 KT1