X. ARMAREA STALPULUI CENTRAL
1. DIMENSIUNI STALP CENTRAL
bst 40 cm 0.8
hst 40 cm 1 - pentru beton greu
2. ALEGEREA MATERIALELOR
a) Betonul C20/25
- rezistenta caracteristica la compresiune: - rezistenta de calcul la compresiune:
ct 1
- rezistenta de calcul la intindere: - rezistenta medie la intindere directa:
fck 20 MPa
c 1.5
fcd
fck
c
13.333MPa
unde c este coeficient de siguranta si are valoarea 1.5.
fctk.0.05 1.5 MPa
fctd
ct fctk.0.05 c
1 MPa
fctm 2.2 MPa
b) Otelul S500 - Bst 500S
- limita de curgere caracteristica: - limita de curgere de calcul:
fyk 500 MPa pentru diametrul nominal 6 ... 28 mm
fyd
fyk
s
435 MPa s
pentru diametrul nominal 6 ... 28 mm
unde s este coeficient de siguranta si are valoarea 1.15.
fyd 435 MPa
3. SECTIUNEA MINIMA SI MAXIMA DE ARMATURA
3.1. Stratul de acoperire cu beton
sl 16mm - diametrul estimat al barei longitudianle :
cmin max sl 15mm 10mm 16 mm - in functie de clasa de expunere XC1 si clasa structurii S4 (durata de viata de 50 ani)
cnom.sl cmin 10mm 26 mm
sw 10mm - diametrul estimat al barei transversale (etrier) :
cmin. max sw 15mm 10mm 15 mm - in functie de clasa de expunere XC1 si clasa structurii S4 (durata de viata de 50 ani)
cnom.sw cmin. 10mm 25 mm
Se verifica respectarea conditiei de acoperire minima cu beton pt etrieri:
cv cnom.sl sw 16 mm cv cnom.sw 1
Pentru a respecta conditia maresc stratul de acoperire cu beton pt armatura longitudinala la
cnom.sl. 35 mm .
cnom max cnom.sl. cnom.sw 35 mm
3.2. Inaltimea utila
d hst cnom sl
2 35.7cm
56
3.3 Ariile minima si maxima
NEd. 857.51kN
As.min.1
0.1NEd.
fyd
1.971cm2
Ac bst hst 1600cm2
As.min.2 0.2% Ac 3.2cm2
max As.min.1As.min.2 3.2cm2
=> As.min.2
As.min.3 0.8% Ac 12.8cm2
- pt cls de ductilitate M
max As.min.2As.min.3 12.8cm2
=> As.min.3
As.min As.min.3 12.8cm2
As.max 0.04Ac 64 cm2
Din notele de calcul a rezultat o sectiune a stalpului de 45x45 cm, dar cum se va vedea din calculul static este suficienta si o sectiune de 40x40 cm.
Localitatea in care este amplasata cladirea este Satu Mare cu ag 0.12 , ag 0.16 1 => clasa
de ductilitate M.
lst 4.48m - lungimea stalpului central de la parter
lst.1 3.42m - lungimea stalpului central de la nivelul 1
lst.2 3.42m - lungimea stalpului central de la nivelul 2
Eforturile axiale din calculul static:
NEd.s.p.inf 857.51kN NEd.s.1.inf 543.68kN NEd.s.2.inf 244.72kN
NEd.s.p.sup 833.77kN NEd.s.1.sup 525.56kN NEd.s.2.sup 226.60kN
NEd max NEd.s.p.inf NEd.s.p.sup NEd.s.1.inf NEd.s.1.sup NEd.s.2.inf NEd.s.2.sup 857.51kN
5. ARMAREA LONGITUDINALA
5.1 Armarea longitudinala pentru stalpul de la parter
a) Momente de calcul
MEd.sus.x 67.74kN m
MEd.jos.x 90.05kN m
MEd.sus.y 71.36kN m
MEd.jos.y 91.46kN m
Lungimea de flambaj: lo 0.5 lst 2.24m
57
b) Determinarea momentelor de ordinul 1:
ei maxlo
400
hst
30 20mm
20 mm
M01.x min MEd.sus.x MEd.jos.x ei NEd 84.89kN m
M02.x max MEd.sus.x MEd.jos.x ei NEd 107.2kN m
M01.y min MEd.sus.y MEd.jos.y ei NEd 88.51kN m
M02.y max MEd.sus.y MEd.jos.y ei NEd 108.61kN m
c) Determinarea coeficientului de zveltete pe directia x si pe directia y
ibst hst
3
12 bst hst11.547cm - raza de giratie
lo
i19.399 - coeficientul de zveltete al stalpului
x 19.399 y 19.399
A 0.7 - coeficient ce tine seama de efectul curgerii lente a metalului
B 1.1 - coeficient ce tine seama de cantitatea de armatura in sectiune
NEd
bst d fcd0.45
rm.x
M01.x
M02.x
0.792 rm.y
M01.y
M02.y
0.815
Cx 1.7 rm.x 0.908 Cy 1.7 rm.y 0.885
Cx Cy - coeficienti ce tin seama de forma diagramei de moment pe inaltimea stalpului
nNEd
fcd bst hst0.402
lim.x
20 A B Cx
n22.058 lim.y
20 A B Cy
n21.498
x lim.x 1 y lim.y 1
lim - valoarea limita a coeficientului de zveltete
Deoarece lim nu se ia in considerare efortul de ordinul II la verificarea sectiunii stalpului .
Am ales 8Φ16 cu Asl.tot.eff 16.08cm2
.
nNEd.
0.7 Ac fcd Asl.tot.eff fyd 0.432 1.dr.sup linterp
0.100
0.500
300
150
0.328
214.5
Asl.tot.eff fyd Ac fcd
0.328
Conform SR EN 1992-1-2-2006 - Calculul comportarii la foc (a structurilor de beton) pentru rezistenta la foc impusa de 60 minute (R60), n 0.432 si 0.328 rezulta bst.min 310 mm si
distanta minima intre axele armaturilor si suprafata stalpului de 30 mm .
1.dr.sup. linterp0.100
0.500
500
250
0.328
357.5
58
My
91.46
91.46
71.36
71.36
kN m Mx
90.04
90.05
67.74
67.74
kN m NEd..
857.51
543.68
244.72
226.60
kN
1.dr.sup.. linterp0.3
0.5
215
357
0.432
308.72 Rd 1.0 - pentru clasa de ductilitate M ( conform P100-2006, punctul 5.4.3.3)
Mdc Rd M'Ed min 1M Rb
M Ed
M'Ed
M2.stg.sup 64.43kN m M2.dr.inf 47.75kN m
Mcap.2.stg.sup 74.423kN m Mcap.2.dr.inf 51.298kN m
M Rb.x M2.stg.sup M2.dr.inf 112.18kN m
M Edb.x Mcap.2.stg.sup Mcap.2.dr.inf 125.721kN m
rapx
M Rb.x
M Edb.x
0.892
Mdc.x Rd Mx min 1 rapx
80.342
80.351
60.444
60.444
kN m
M2.stg.sup. 80.76kN m M2.dr.inf. 46.02kN m
Mcap.2.stg.sup. 87.469kN m Mcap.2.dr.inf. 51.298kN m
M Rb.y M2.stg.sup. M2.dr.inf. 126.78kN m
M Edb.y Mcap.2.stg.sup. Mcap.2.dr.inf. 138.767kN m
rapy
M Rb.y
M Edb.y
0.914
Mdc.y Rd My min 1 rapy
83.559
83.559
65.196
65.196
kN m
x
Mdc.x
bst hst2
fcd
9.415 105
9.416 105
7.083 105
7.083 105
y
Mdc.y
bst hst2
fcd
9.792 105
9.792 105
7.64 105
7.64 105
NEd..
bst hst fcd
0.402
0.255
0.115
0.106
1 max x y 9.792 105
2 min x y 9.792 105
Procentul de armare total: tot 0.1
59
As.tot tot bst hstfcd
fyd
4.904cm2
Am ales 8Φ16 cu As.tot.eff 16.08cm2
.
As.ramura
As.tot
41.226cm
2 Am ales 4Φ16 cu As.ram.eff 8.08cm
2 .
As.tot.eff As.min 1 unde As.min 12.8cm2
Forta axiala capabila la compresiune centrica:
NRd bst hst fcd As.tot.eff fyd 2832.813kN
aNEd
NRd
0.303 rezulta linterp0.1
0.7
1
1.5
a
1.169
Verificare: MRd.y 2 As.ram.eff fyd 0.9 d 225.861kN m Med.y 91.46kN m
Med.x 90.05kN m MRd.x 2 As.ram.eff fyd 0.9 d 225.861kN m
Med.y
MRd.y
Med.x
MRd.x
0.689 <1 OK
5.2 Armarea longitudinala pentru stalpul de la etaj
a) Momente de calcul
MEd.sus.x. 58.78kN m
MEd.jos.x. 50.26kN m
MEd.sus.y. 60.67kN m
MEd.jos.y. 52.78kN m
Lungimea de flambaj: lo. 0.5 lst.1 1.71m
b) Determinarea momentelor de ordinul 1:
ei. maxlo.
400
hst
30 20mm
20 mm
M01.x. min MEd.sus.x. MEd.jos.x. ei. NEd 67.41kN m
M02.x. max MEd.sus.x. MEd.jos.x. ei. NEd 75.93kN m
M01.y. min MEd.sus.y. MEd.jos.y. ei. NEd 69.93kN m
M02.y. max MEd.sus.y. MEd.jos.y. ei. NEd 77.82kN m
c) Determinarea coeficientului de zveltete pe directia x si pe directia y
ibst hst
3
12 bst hst11.547cm - raza de giratie
.
lo.
i14.809 - coeficientul de zveltete al stalpului
x. . 14.809 y. . 14.809
60
A 0.7 - coeficient ce tine seama de efectul curgerii lente a metalului
B 1.1 - coeficient ce tine seama de cantitatea de armatura in sectiune
rm.x.
M01.x.
M02.x.
0.888 rm.y.
M01.y.
M02.y.
0.899
Cx. 1.7 rm.x. 0.812 Cy. 1.7 rm.y. 0.801
Cx Cy - coeficienti ce tin seama de forma diagramei de moment pe inaltimea stalpului
n'NEd
fcd bst hst0.402
lim.x.
20 A B Cx.
n'19.729 lim.y.
20 A B Cy.
n'19.466
x. lim.x. 1 y. lim.y. 1
lim - valoarea limita a coeficientului de zveltete
Deoarece lim nu se ia in considerare efortul de ordinul II la verificarea sectiunii stalpului .
Am ales 8Φ16 cu Asl.tot.eff. 16.08cm2
.
n''NEd.
0.7 Ac fcd Asl.tot.eff. fyd 0.432
'Asl.tot.eff. fyd
Ac fcd0.328
Conform SR EN 1992-1-2-2006 - Calculul comportarii la foc (a structurilor de beton) pentru rezistenta la foc impusa de 60 minute (R60), n 0.432 si 0.328 rezulta bst.min. 310 mm si
distanta minima intre axele armaturilor si suprafata stalpului de 30 mm .
My.
91.46
91.46
71.36
71.36
kN m Mx.
90.04
90.05
67.74
67.74
kN m NEd'
857.51
543.68
244.72
226.60
kN
Rd 1 - pentru clasa de ductilitate M ( conform P100-2006, punctul 5.4.3.3)
Mdc Rd M'Ed min 1M Rb
M Ed
M'Ed
M2.stg.sup 64.43kN m M2.dr.inf 47.75kN m
Mcap.2.stg.sup 74.423kN m Mcap.2.dr.inf 51.298kN m
M Rb.x. M2.stg.sup M2.dr.inf 112.18kN m
M Edb.x. Mcap.2.stg.sup Mcap.2.dr.inf 125.721kN m
rapx.
M Rb.x.
M Edb.x.
0.892
Mdc.x. Rd Mx. min 1 rapx.
80.342
80.351
60.444
60.444
kN m
61
M2.stg.sup. 80.76kN m M2.dr.inf. 46.02kN m
Mcap.2.stg.sup. 87.469kN m Mcap.2.dr.inf. 51.298kN m
M Rb.y. M2.stg.sup. M2.dr.inf. 126.78kN m
M Edb.y. Mcap.2.stg.sup. Mcap.2.dr.inf. 138.767kN m
rapy.
M Rb.y.
M Edb.y.
0.914
Mdc.y. Rd My. min 1 rapy.
83.559
83.559
65.196
65.196
kN m
x
Mdc.x
bst hst2
fcd
9.415 105
9.416 105
7.083 105
7.083 105
y
Mdc.y
bst hst2
fcd
9.792 105
9.792 105
7.64 105
7.64 105
NEd'
bst hst fcd
0.402
0.255
0.115
0.106
1. max x y 9.792 105
2. min x y 9.792 105
Procentul de armare total: tot 0.1
As.tot. tot bst hstfcd
fyd
4.904cm2
Am ales 8Φ16 cu As.tot.eff. 16.08cm2
.
As.ramura.
As.tot
41.226cm
2 Am ales 4Φ16 cu As.ram.eff. 8.08cm
2 .
As.tot.eff As.min 1 unde As.min 12.8cm2
Forta axiala capabila la compresiune centrica:
NRd. bst hst fcd As.tot.eff. fyd 2832.813kN
aNEd
NRd
0.303 rezulta linterp0.1
0.7
1
1.5
a
1.169
Verificare: MRd.y. 2 As.ram.eff. fyd 0.9 d 225.861kN m Med.y. 91.46kN m
Med.x. 90.05kN m MRd.x. 2 As.ram.eff. fyd 0.9 d 225.861kN m
Med.y.
MRd.y.
Med.x.
MRd.x.
0.689 <1 OK
62
5.4 Distanta minima si efectiva dintre bare
max sl 16 mm dg 16 mm - dimensiunea maxima a agregatului
snv max max dg 5 mm 20 mm 21 mm - distanta minima dintre barele longitudinale
3Φ16 : seff
bst 2 cnom 3 sl 2
141 mm
seff - distanta efectiva dintre barele longitudinale situate pe o latura a sectiunii transversale a stalpului
ssl.max 200 mm - distanta maxima dintre barele longitudinale
min 12 mm - diametrul minim pentru barele longitudinale
Coeficientul minim si maxim de armare longitudinala (P100-2006, punctul 5.4.4.2.2, (2) :
min 0.008
max 0.04
eff
As.tot.eff.
bst d0.011
min eff max 1
Avand in vedere ca inaltimea celor 2 etaje (nivel 1 si 2) este egala aria armaturii longitudinale este aceeasi. Aria armaturii longitudinale rezultata din calcul este aceeasi si pentru parter, prin urmare cel mai solicitat stalp, stalpul central 40x40 cm situat la intalnirea axelor B si 2, se armeaza pe intreaga sa
lungime, adica din fundatie pana la planseul terasa inclusiv, cu 8Φ16 avand As.tot.eff 16.08cm2
.
63
6. ARMAREA TRANSVERSALA
6.1 Otelul S255 - OB37
- limita de curgere caracteristica: - limita de curgere de calcul:
fyk. 255 MPa pentru diametrul nominal 6 ... 12 mm
unde s 1.15 este coeficient de siguranta.
fywd
fyk.
s
221.739MPa pentru diametrul nominal 6 ... 28 mm
6.2 Coeficientul minim de armare transversala cu etrieri
min.etr 0.0035Ac 5.6cm2
- in zona critica a stalpilor de la baza lor, la primul nivel
min.etr. 0.0025Ac 4 cm2
- in restul zonelor critice
fck 20 MPa fyk 500 MPa
w.min 0.08fck
fyk
w.min 0.0820
500 0.0007
Cantitatea maxima de armatura transversala:
Cantmax
Asw
s
.max cw 1 - pentru beton armat
0.6 1fck
200
1 0.6 120
200
0.54
Cantmax 0.5cw 1 bstfcd
fywd
0.649cm
6.3 Distanta minima dintre etrieri
dbl 14 mm
Diametrul etrierilor pentru armarea stâlpilor pentru M :
dbw. 0.4 dbl 5.6 mm deci dbw 6 mm
bo bst 2 cnom 2 dbw 318 mm - lăţimea utilă a secţiunii transversale
smin.etr minbo
2175 mm 8 dbl
112 mm - distanta minima dintre etrieri smin 150 mm
6.4 Zona critica
Calcul lungimii critice pentru stalp - zone potenţiale de formare a articulaţiilor plastice, unde stâlpul va fi armat transversal suplimentar (distanţe mai mici între etrieri), se face in functie de clasa de ductilitate - M.
Nivel 1(parter) : lcl.p 4.10 m lcr.p max hst
lcl.p
6 450 mm
68.333cm
Nivel 2(etaj) : lcl.e 2.97 m lcr.e max hst
lcl.e
6 450 mm
49.5cm
64
Coeficient functie de clasa de ductilitate: Rd 1 pentru clasa M de ductilitate
Forţa de calcul de întindere din armătură: Fs fyd As.tot.eff 699.48kN
xFs
fcd bst163.941mm
ds hst 2 cnom 2 dbw dbl 30.4 cm
z ds x
2 23.842cm
Moment capabil în stâlp : MRc. Fs z 166.773kN m
Superior :
Mcap.2.stg.sup 74.423kN m
Mcap.2.dr.inf 51.298kN m
M Rb.x. Mcap.2.stg.sup Mcap.2.dr.inf 125.721kN m
M Rc.x.sus MRc. 166.773kN m
rapx.
M Rb.x.
M Rc.x.sus
0.754
Mdc.x.sus Rd MRc. min 1 rapx. 125.721kN m
Mcap.2.stg.sup. 87.469kN m
Mcap.2.dr.inf. 51.298kN m
M Rb.y. Mcap.2.stg.sup. Mcap.2.dr.inf. 138.767kN m
M Rc.y.sus MRc. 166.773kN m
rapy.
M Rb.y.
M Rc.y.sus
0.832
Mdc.y.sus Rd MRc. min 1 rapy. 138.767kN m
Inferior :
Mdc.x.jos Rd MRc. 166.773kN m
Mdc.y.jos Mdc.x.jos 166.773kN m
Vx
Mdc.x.sus Mdc.x.jos
lcl.p
71.34kN Vy
Mdc.y.sus Mdc.y.jos
lcl.p
74.522kN
Vx. 36.34kN Vy. 35.21kN
VEd.x max Vx Vx. 71.34kN VEd.y max Vy Vy. 74.522kN
VEd max VEd.x VEd.y 74.522kN
65
6.5 Calculul armaturii transversale
VEd 74.522kN
VRd.c cRd.c k'1 100 1 fck
1
3 k1 cp
bst d
unde : fck 20 MPa cRd.c
0.18
c
0.12 cRd.c 0.12
1
NEd 857.51kN cp..
NEd
Ac
5.359N
mm2
cp. mincp.. 0.2fcd 2.667N
mm2
k'1 1200
d
1mm
1.748 k'1 2 1
k1 0.15
1
As.tot.eff.
bst d0.011 1 0.02 1
VRd.c 0.121 1.748 100 0.009 20( )
1
3 0.152.667
N
mm2
400 mm304 mm 115.493kN
VRd.c - forta taietoare capabila a elementului fara armatura transversala specifica
VRd.c.min. min k1 cp. bst d min unde min.. 0.035k
3
2 fck k
min. 0.035k'1
3
2 20
N
mm2
361.888kN
m2
VRd.c.min min. bst ds 44.006kN (valoarea minima a fortei taietoare capabila fara armatura specifica)
VRd.c VRd.c.min 1
VRd.c VEd 1 - pentru ca solicitarea de calcul este mai mica decat capacitatea portanta a stalpului fara armatura specifica nu este necesar calculul armaturii transversale, ea dispunandu-se constructiv
Se determina capacitatea portanta a bielei comprimate de beton pentru ctg(θ)=2.5 .
VRd.max cw.1 bst z 1 fcd1
2.51
2.5
z 23.842cm
cw.1 1
VRd.max cw.1 bst z 1 fcd1
2.51
2.5
236.779kN
VEd VRd.c VRd.max 1 VRd.c 115.493kN
VEd 74.522kN
VRd.max 236.779kN
66
Etr. Φ10: Asw 2 113 mm
22.26cm
2 - 2 ramuri de forfecare
fywd 221.739MPa ctg 2.5
s1
Asw z fywd ctg
VEd
400.827mm
seff.1 300mm seff.1 smin 1
Distanta dintre etrieri calculata este mai mica sau egala decat distanta maxima.
smax 300 mm seff.1 smax 1
Calculam capacitatea portanta a etrierilor la forta taietoare.
VRd.s
Asw
seff
z fywd ctg 211.846kN
VRd.max VEd 1 VRd.max VRd.s 1
Procentul de armare efectiv:
Pe lungimea zonei critice de la parter lcr.p 68.333cm avem distanta dintre etrieri de
smin 150 mm si coeficientul minim de armare min.etr.. 0.0035 .
smin 150 mm w.eff.
Asw
sminbst0.0038 w.eff. min.etr.. 1
w.min. 0.0820
500 0.0007
seff.1. 300 mm w.eff.1
Asw
seff.1. bst0.0019 w.eff.1 w.min. 1
In final au rezultat etrieri Φ10/150mm OB37 pe lcr.p 68.333cm , Φ10/150mm OB37 pe
lcr.e 49.5 cm si Φ10/300mm in rest.
7. ANCORAREA ARMATURILOR
Armaturile longitudinale din stalp se ancoreaza la efortul unitar capabil al barei.
lbd lb.rqd 1 2 3 4 5 (lungimea de ancorare de proiectare necesara)
- pentru barele Φ16: 16 16mm
lb.rqd 0.25fyd
fbd
unde lb.rqd - lungimea de ancorare de baza
fbd - efortul unitar de aderenta considerat constant pe lungimea de ancorare.
lb.rqd.16 48 16 76.8 cm
1 1.16 1 - ancoraj drept
2 2.16 1
3 K16 0.1 16
0.25As.tot.eff
As.tot.eff
0.25 3.16 1 K16 16 0.975
4 4.16 1 - nu avem armaturi sudate
5 1 0.043 0.88 5.16 0.880
2.16 3.16 5.16 0.7 0
lbd.16 lb.rqd.16 1.16 4.16 0.7 53.76cm (lungimea de ancorare efectiva)
lbd.min.16 max 0.3 lb.rqd.16 10 16 100mm 23.04cm (lungimea minima de ancorare)
lbd.min.16 lbd.16 1
lbd.16.eff 60 cm