+ All Categories
Home > Documents > ADSORPTIE

ADSORPTIE

Date post: 01-Jul-2015
Category:
Upload: xenia1970
View: 155 times
Download: 7 times
Share this document with a friend
18
CHILLERE CU ADSORBTIE RECUPERARE DE CALDURA RACIRE SOLARA
Transcript
Page 1: ADSORPTIE

CHILLERE CU ADSORBTIE

RECUPERARE DE CALDURARACIRE SOLARA

MaxiComp - Innovative Integrated Engineering Solutions

Page 2: ADSORPTIE

ANALIZA TEHNICA

Caracteristici generaleParametrii de functionareGama de capacitatiPrincipii de functionareReferinteAdsorbtie vs AbsorbtieAdsorbtie vs Compresie mecanica

Page 3: ADSORPTIE

ANALIZA ECONOMICA

Consum energeticCosturi de intretinere si exploatareAdsorbtie vs Compresie

Page 4: ADSORPTIE

Gama de capacitati

4817.004817.004817.004817.004120.004120.003440.003440.003410.003410.003575.003575.00mmL

2863.002863.002863.002863.002863.002863.002910.002910.002620.002620.002385.002385.00mmHDim

4572.004572.002305.002305.002275.002275.001955.001955.002010.002010.001800.001800.00mmW

30.0030.0015.0015.0012.1012.109.209.207.507.505.005.00TonEMPTYWEIGHT

9.609.609.609.609.609.609.409.409.409.409.409.40L/minAirSupply

5.005.005.005.005.005.005.005.005.005.005.005.00Kg/cm2gAir Press.Air

0.400.400.400.400.200.200.200.200.200.200.200.20KWVAC. P

0.500.500.500.500.500.500.500.500.500.500.500.50KVAPOWER CAPPower

60.0060.0060.0060.0060.0060.0060.0060.0060.0060.0060.0060.00HZFREQElectric

200.00200.00200.00200.00200.00200.00200.00200.00200.00200.00200.00200.00VVOLT

2308.171322.57758.971070.58607.18856.47379.48535.29265.64374.70110.03154.61KWHeat Req.Water

4.404.402.202.201.761.761.101.100.770.770.330.33m3/minFLOWHot

82.4885.6985.0683.0385.0683.0385.0683.0385.0683.0385.1583.18COUT

90.0090.0090.0090.0090.0090.0090.0090.0090.0090.0090.0090.00CIN

3665.382183.571286.941700.081029.551360.07643.47850.04450.43595.03182.47240.98KW

8.008.004.004.003.203.202.002.001.401.400.570.57m3/minFLOWWater

31.5733.3134.0135.4934.0135.4934.0135.4934.0135.4934.0335.51COUTCooling

25.029.429.429.429.429.429.429.429.429.429.429.4CIN

3.894.111.511.801.211.440.760.900.530.630.210.25m3/minFLOWWater

6.73.006.76.76.76.76.76.76.76.76.76.7COUTChilled

11.706.0011.7011.7011.7011.7011.7011.7011.7011.7011.7011.70CIN

0.590.650.700.590.700.590.700.590.700.590.660.56COP

1357.21861.00527.97629.50422.38503.60263.98314.75184.79220.3372.4486.37KWCAPACITY

EcoStandardStandardEcoStandardEcoStandardEcoStandardEcoStandardEcoTYPE

ADCM1-360ADCM1-180ADCM1-145ADCM1-090ADCM1-060ADCM1-025Model

Page 5: ADSORPTIE

Referinte

Solar2 x 350KWGrecia

Co-generare / Solar350 kWGreciaSarantis

Co-generare175 kWBirkenfeldUniversity

Co-generare175 kWSchweinfurthUniversity

Termoficare350 kWVölklingenFernwärmeverbund

Co-generare / solar70 kWDessauUmweltbundesamt

Termoficare350 kWAugsburgUmweltamt

Termoficare150 kWFreiburgUniklinik

Termoficare350 kWLudwigshafenStadtwerke

Termoficare150 kWWertheimStadtwerke

Termoficare70 kWMannheim GKM

co-generator350 kWNeuwiedStadtwerke

Termoficare350 kWLiesdorfIKEA

Co-generare175 kWUnnaKarstadt

Co-generare350 kWUnnaKarstadt

Termoficare350 kWSaarbrückenStadtwerke

Termoficare350 kWKasselStadtwerke

Termoficare / Solar70 kWDresden Götz GmbH

Co-generare / Solar70 kWWürzburgGötz GmbH

Sursa de calduraCapacitateOrasBeneficiar

Page 6: ADSORPTIE

San Jose (USA)

Page 7: ADSORPTIE

Fresno (USA)

Page 8: ADSORPTIE

Charlotte (USA)

Page 9: ADSORPTIE

Tesco – Londra (UK)

Page 10: ADSORPTIE

Nagano ( Japonia)

Page 11: ADSORPTIE

Adsobtie vs Absorbtie

NU. Chillerele cu absorbtie nu pot functiona8000 h/an datorita operatiunilor de intretinereexecutate la fiecare 3000h.Solutia de Li-Br se dilueaza pe parcursul operarii, astfel incatsolutie noua trebuie adaugata. De asemeneabalanta inhibitorilor de coroziune pe baza de Crsau Mo se dezechilibreaza, iar solutia Li-Br poate devini extrem de coroziva. O noua seriede analize si noi cantitati de inhinbitori trebuiescadaugate la fiecare 3000h, pentru a mentineechilibrul chimic. Daca chillerul nu este intretinutcorespunzator poate fi scos din functiune in maiputin de 4 ani.

DAFunctionare8000h/an

NU. Concentratia solutiei Li-Br creste pe duratafunctionarii. Un proces de dilutie este necesar

zilnic.

DAFunctionare continua 24h/zi

80 – 100oC (sau mai mult)50% capacitate la 80oC

Functionare imposibila la 60oC

50 – 90oC (sau mai mult)70% capacitate la 70oC

Temperatura sursacalda

AbsorbtieAdsorbtieComparatie

Page 12: ADSORPTIE

Adsobtie vs Absorbtie (cont)

1 / 15 minuteCiclu de dilutie

30 minute7 minutePornire dupa oprirede lunga durata

Minimum 22oC.Temperatura apei de racire trebuie mentinute in

limite stabile.Reglajul temperaturii apei de racire cu

ventile cu 3 cai este necesar.

Indiferent. COP cresteodata cu scadereatemperaturii apei de racire. Variatiile de temperatura nuinfluentea functionareaechipamentului.

Temperatura apei de racire

0,70,7COP nominal

Controlul capacitatii este sofisticat.Pentru a urmarii variatii ale sarcinii de racire

intre 100% si 25%, sistemul cu absorbtienecesita tancuri de apa calda si apa racita. Controlul PID este necesar suplimentar pentrucontrolul apei calde, a celei de racire si a apeiracite. Daca temperaturile nu sunt stabile, echipamentul se opreste.

Standard. Se realizeaza in 7 trepte de capacitate

Sarcina minima

AbsorbtieAdsorbtieComparatie

Page 13: ADSORPTIE

Adsobtie vs Absorbtie (cont)

Apa distilataApa de la reteaRefrigerent

Ventile cu 3 cai, modulanteVane flutureVentile automate

DA.Functionare continua;

NUPompa absorbent

DA.Functionare continua;

Pompa ermetica

DAFunctionare discontinua peperioada reducerii capacitatii

Pompa refrigerent( APA)

DADAPompa de vacuum

Solutie Li-Br7,60 Euro / ltr

Silica Gel, inclus in echipament

Adsorbent/Absorbent

AbsorbtieAdsorbtieComparatie

Page 14: ADSORPTIE

Adsobtie vs Absorbtie (cont)

CHIMICAMECANICANatura defectiunilor

Ridicate- Analize periodice ale solutiei;

-Revizii pompe;-Revizii sistem de control;

- Revizia cazanului de back-up;-Revizii si reparatii la schimbatoarele de

caldura;- Verificari de etanseitate periodice.

Scazute-Se verifica nivelul uleiului in pompa de vacuum;- Schimbarea etansarilor la vanelefluture, la 3 ani.

Costuri de mentenanta

DA, pentru a asigura continuitateatemperaturii sursei calde

NUCazan de back-up

Capacitate egala cu cea de racire+ caldura introduse

Capacitate egala cu cea de racireTurn de racire

AbsorbtieAdsorbtieComparatie

Page 15: ADSORPTIE

Adsobtie vs Absorbtie (cont)

DA-La temperatura scazuta a apei de racire;

- Scapari de aer in masina;-Defecte in sistemul de control;

-Sursa de caldura cu functionaredefectuoasa/ discontinua;

- Defecte in sistemul de valve;-Pierderea controlului sistemului de dilutie

a solutiei

NUCristalizare

DA, PUTERNICAIn conditiile cele mai bune de intretinererecomandate de fabricant, fasciculul de tevial schimbatoarelor trebuie inlocuit dupa 2,5 –3 ani de functionare, in conditiile operarii a 8000h/an.

NUCoroziune

DA, cu metale greleNUInhibitori de corosiune

AbsorbtieAdsorbtieComparatie

Page 16: ADSORPTIE

Adsobtie vs Absorbtie (cont)

7 – 9 ani> 20 aniDurata estimata de viata

4-5 aniAbsorbentul este corosiv, cu continut de

metale grele , implica costuri suplimentarela depozitare ca deseuri

NUFrecventa de inlocuire a adsorbentului/absorbentului

Incerta3aniAmortizare estimata

AbsorbtieAdsorbtieComparatie

Page 17: ADSORPTIE

Adsobtie vs Compresie mecanica

Ridicate.In special datorita consumului energetic

crescut

Foarte scazuteCosturi de operare

Ridicat>80dB (A)

Foarte scazut<50dB(A)

Nivel de zgomot

RidicateEste necesara o intretinere periodica

-Analiza anuala a calitatii uleiului.-Schimb de ulei la 15000 ore functionare .

• Curatare anuala a condensatorului; -Functie de tipul compresorului numarul

mare de piese in miscare conduce la inlocuirea periodica a supapelor,

segmentilor, lagarelor, rulmentilor.-Verificarea anuala a etansarilor, si

completari cu freon pentru chillerele aflate in exploatare de o perioada mai indelungata.

-.

ScazuteLipsa pieselor in miscarecontribuie la reducereasubstantiala a costurilor de intretinere.- Se impune schimbareala 5 ani a uleiului pompeide vacuum;- Curatarea anuala a condensatorului.

Costuri de intretinere

Compresie mecanicaAdsorbtieComparatie

Page 18: ADSORPTIE

Adsobtie vs Compresie mecanica

Dezafectarea trebuie realizata de personal calificat. Freonul si uleiul trebuie recuperate sivalorificate ca deseuri.

Usoare – nu necesitacheltuieli suplimentarepentru dezafectare

Casare / Dezafectare

PeriodiceNumarul ridicat de piese in miscare conducla defectiuni periodice, neprevazute ale ventilatoarelor si compresoarelor.

RareDatorita numarului foartescazut de piese in miscare.

Probleme in functionare

Compresie mecanicaAdsorbtieComparatie